Open Loop Auxiliary Cooling Water Booster Pump Unit 4B PLTU Asam Asam

Anwar, Khairil and Antono, Vendy and Wahyuningsih, Utami (2021) Open Loop Auxiliary Cooling Water Booster Pump Unit 4B PLTU Asam Asam. Diploma thesis, ITPLN.

[thumbnail of Tugas akhir khairil anwar.pdf] Text
Tugas akhir khairil anwar.pdf
Restricted to Repository staff only

Download (3MB)

Abstract

Sistem pendinginan PLTU ini dibagi menjadi 2 sistem air yaitu pendinginan utama dan pendinginan Pendukung (Open Loop auxiliary cooling water). Kegunaan dari sistem pendinginan utama ialah untuk menyuplai air yang dibutuhkan untuk mengkondensasikan bekas uap dan didalam kondensor drain up. Lalu untuk kegunaan pendinginan bantu yaitu menyediakan mendinginkan air pada “Heat Exchanger” air pendingin ini atau pendingin bantu (auxiliary cooling water).
Sistem pendinginan pun butuh yang namanya perbaikan atau perawatan yang biasa dilakukan agar mencegah terjadinya kerusakan atau perbaikan rutin yang terjadi pada sistem pendinginan. Kerusakan yang terjadi pada bagian (Open Loop auxiliary cooling water) terjadi dikarenakan adanya vibrasi yang tinggi, mengakibatkan mesin ini mengalami trouble, pompa ini memiliki vibrasi yang tinggi sekitar 6.71 mm/s dan sudah dikategorikan dalam zona D jadi pompa ini pun baru dilakukan inspection dilakukan pemeliharaan dan ditemukan bahwa dari vibrasi yang tinggi Diakibatkan oleh Unbalance.
Sesudah dilakukanya balancing pada pompa Open Loop Auxiliary Cooling Water Booster Pump vibrasi menurun menjadi dari data RMS 1.85 mm/s. Nilai vibrasi yang terjadi pada pompa diklasifikasikan dalam zona ‘A’ sesuai dengan standar ISO 10816-3 dari pompa dengan daya 90 Kw. Setelah dilakukan perhitungan dapatlah selisih penurunan vibrasi sebesar 6.667 mm/s dan besar persentase penurunan vibrasi adalah 78.57%.

The PLTU cooling system is divided into 2 systems, namely main cooling and supporting cooling (Open Loop auxiliary cooling water). The purpose of the main cooling system is to ensure the air required to compress the exhaust steam and in the condenser drain up. Then for cooling purposes, namely to provide cooling water in the "Heat Exchanger" of this cooling water or auxiliary cooling water. The cooling system also needs repairs or maintenance that is usually done so that damage or routine repairs occur in the cooling system.

the damage that occurs in the (Open Loop auxiliary cooling water) section occurs due to high vibrations, causing this machine to have problems, this pump has a high vibration of about 6.71 mm/s and has entered zone D so this pump has just been done inspection carried out maintenance and found that from high vibration Caused by Unbalance. Before balancing the Open Loop Auxiliary Cooling Water Booster Pump, the vibration decreased to RMS data of 1.85 mm/s. The vibration values that occur in the pump are classified in zone 'A' according to the ISO 10816-3 standard of pumps with a power of 90 Kw. After calculating the difference in the vibration reduction of 6.667 mm/s and the percentage of vibration reduction of 78.57%.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Open Loop, Unbalance, vibration, Cooling Water Booster Pump, Poros Sentrifugas Multistage, Sistem Pendingin, Water Pump, PLTU
Subjects: Bidang Keilmuan > Maintenance
Bidang Keilmuan > Mechanical Engineering
Bidang Keilmuan > Pump
Skripsi
Bidang Keilmuan > Teknik Mesin
Divisions: Vokasi > D3 Teknologi Mesin
Depositing User: Yudha Formanto
Date Deposited: 28 Aug 2025 07:54
Last Modified: 28 Aug 2025 08:05
URI: https://repository.itpln.ac.id/id/eprint/331

Actions (login required)

View Item
View Item