Abstract

Sering kali, masalah terjadi dalam penyaluran energi listrik bertegangan tinggi karena kegagalan isolasi, terutama isolasi cair. Apabila pemanasan terjadi secara terus-menerus isolasi akan mengalami pemburukan yang dapat menyebabkan kegagalan isolasi dan mengakibatkan terjadinya tegangan tembus, maka dari itu perlu diketahui kemampuan kerja isolasi yang digunakan. Minyak transformator adalah bahan isolasi cair yang dipakai pada peralatan trafo untuk isolasi dan pendingin. Penelitian ini bertujuan untuk mengetahui pengaruh penambahan antioksidan pada perubahan suhu terhadap nilai tegangan tembus minyak jarak. Dengan menggunakan metode kuantitatif pengujian dilakukan menggunakan standar IEC 60-156:2018. Hasil dari penelitian ini menunjukkan bahwa semakin tinggi suhu yang digunakan maka akan semakin tinggi nilai tegangan tembus yang dihasilkan. Nilai tegangan tembus minyak jarak murni mencapai standar nilai isolasi yaitu 30 kV/2,5 mm. Sedangkan untuk pengujian penambahan antioksidan dapat diketahui bahwa semakin banyak antioksidan yang ditambahkan, maka akan semakin kecil nilai tegangan tembus yang ditunjukkan. Pada penelitian ini pengaruh penambahan antioksidan efektif untuk meningkatkan nilai tegangan tembus minyak jarak berada pada konsentrasi 2%

Often, problems occur in the distribution of high voltage electrical energy due to failure of insulation, especially liquid insulation. If heating occurs continuously the insulation will experience deterioration which can cause insulation failure and result in breakdown voltage, therefore it is necessary to know the working capacity of the insulation used. Transformer oil is a liquid insulating material that is used in transformer equipment for insulation and cooling. This research aims to determine the effect of adding antioxidants to changes in temperature on the breakdown voltage value of castor oil. Using quantitative methods, testing was carried out using the IEC 60-156:2018 standard. The results of this research show that the higher the temperature used, the higher the breakdown voltage value produced. The breakdown voltage value of pure castor oil reaches the standard insulation value, namely 30 kV/2.5 mm. Meanwhile, for testing the addition of antioxidants, it can be seen that the more antioxidants added, the smaller the breakdown voltage value shown. In this study, the effect of adding effective antioxidants to increase the breakdown voltage value of castor oil was at a concentration of 2%.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Isolasi Cair, tegangan tembus, kegagalan isolasi Liquid insulation, breakdown voltage, insulation failure
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 04 Nov 2025 03:46
Last Modified: 04 Nov 2025 03:46
URI: https://repository.itpln.ac.id/id/eprint/3327

Actions (login required)

View Item
View Item