Hidayat, Novia Ramadhani and Munir, Nur Al Anshari (2024) ANALISIS KONDISI BELITAN, BUSHING DAN ISOLASI PADAT TRANSFORMATOR GT 3.1 BLOK 3 PLTGU MUARA KARANG. Diploma thesis, ITPLN.
SKRIPSI 201911191 NOVIA RAMADHANI HIDAYAT.pdf
Restricted to Registered users only
Download (4MB)
Abstract
Penelitian ini bertujuan untuk menganalisis kondisi belitan, bushing, dan isolasi padat pada transformator GT 3.1 di Blok 3 PLTGU Muara Karang. Asesmen ini mencakup pengujian resistansi isolasi, indeks polarisasi, pengujian resistansi DC, faktor disipasi (Tan Delta), analisis arus eksitasi, analisis respons dielektrik, dan rasio belitan. Pada penelitian ini digunakan metode kuantitatif komparatif untuk menganalisis kondisi belitan, bushing dan isolasi padat transformator GT 3.1 Blok 3 Muara Karang. Hasil pengujian resistansi isolasi menunjukkan nilai yang sesuai dengan standar IEEE C57.152-2013, dengan nilai resistansi lebih dari 100 MΩ dan indeks polarisasi lebih dari 1,25. Pengujian resistansi DC menunjukkan deviasi yang rendah, di bawah batas maksimal 5%. Nilai Tan Delta untuk keseluruhan trafo dan bushing berada dalam batas yang ditetapkan oleh standar, menunjukkan kondisi isolasi yang baik. Analisis arus eksitasi menunjukkan pola arus yang normal sesuai standar, dan hasil analisis respons dielektrik menunjukkan kategori minyak yang sangat baik. Pengujian rasio belitan menunjukkan deviasi yang sangat kecil, berada di bawah batas maksimal 0,5%. Secara keseluruhan, hasil asesmen menunjukkan bahwa transformator GT 3.1 dalam kondisi normal dan masih sesuai dengan standar yang berlaku. Penelitian ini merekomendasikan pengujian DGA secara rutin, pemantauan suhu trafo, dan asesmen listrik berkala untuk memastikan kondisi operasional yang optimal.
This research aims to analyze the condition of the windings, bushings and solid insulation on the GT 3.1 transformer in Block 3 PLTGU Muara Karang. This assessment includes insulation resistance testing, polarization index, DC resistance testing, dissipation factor (Tan Delta), excitation current analysis, dielectric response analysis and turns ratio. In this study, a comparative quantitative method was used to analyze the condition of the windings, bushings and solid insulation of the GT 3.1 Block 3 Muara Karang transformer. The insulation resistance test results show values that comply with the IEEE C57.152- 2013 standard, with a resistance value of more than 100 MΩ and a polarization index of more than 1.25. DC resistance testing shows low deviation, below the maximum limit of 5%. The Tan Delta value for the entire transformer and bushing is within the limits set by the standard, indicating good insulation conditions. Excitation current analysis shows a normal current pattern according to standards, and the results of dielectric response analysis show an excellent oil category. The winding ratio test shows a very small deviation, below the maximum limit of 0.5%. Overall, the assessment results show that the GT 3.1 transformer is in normal condition and still complies with applicable standards. This research recommends routine DGA testing, transformer temperature monitoring, and periodic electrical assessments to ensure optimal operational conditions.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Transformator, belitan, bushing Transformers, windings, bushings |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 05 Nov 2025 03:37 |
| Last Modified: | 05 Nov 2025 03:37 |
| URI: | https://repository.itpln.ac.id/id/eprint/3399 |