ANALISIS KELAYAKAN TAHANAN ISOLASI MENGGUNAKAN PENGUJIAN INDEKS POLARISASI, TANGEN DELTA, DAN BREAKDOWN VOLTAGE PADA TRANSFORMATOR 3 DI GARDU INDUK 150 KV ANCOL

Perdana, Rendy Cahya and Tambunan, Juara Mangapul (2024) ANALISIS KELAYAKAN TAHANAN ISOLASI MENGGUNAKAN PENGUJIAN INDEKS POLARISASI, TANGEN DELTA, DAN BREAKDOWN VOLTAGE PADA TRANSFORMATOR 3 DI GARDU INDUK 150 KV ANCOL. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 201911036 RENDY CAHYA PERDANA.pdf] Text
SKRIPSI 201911036 RENDY CAHYA PERDANA.pdf
Restricted to Registered users only

Download (4MB)

Abstract

Trafo merupakan peralatan statis dimana rangkaian magnetik dan belitan yang terdiri dari 2 atau lebih belitan, secara induksi elektromagnetik, mentransformasikan daya (arus dan tegangan) sistem AC ke sistem arus dan tegangan lain pada frekuensi yang sama (IEC 60076 -1 tahun 2011). Penelitian ini bertujuan untuk megetahui hasil dari pengujian kelayakan isolasi pada trafo unit 3 gardu induk 150kV Ancol yang dimana isolasi pada trafo sangat berpengaruh pada kelayakan operasi dari trafo. Untuk mengetahui kualitas isolasi trafo tenaga digunakan beberapa metode pengujian yaitu pengujian tahanan isolasi, indeks polarisasi, tangen delta dan breakdown voltage. Metodologi penelitian ini menggunakan metode kuantitatif dengan menggunakan data primer dan data sekunder, data primer didapat melalui hasil dari pengujian dengan menggunakan metode pengujian indeks polarisasi, tangen delta dan breakdown voltage. Untuk data sekunder didapat melalui studi literatur yang mewakili standar dari pengujian indeks polarisasi, tangen delta dan breakdown voltage.Hasil pengujian pada tahanan isolasi trafo 3 nilainya melebihi 1 MΩ maka dapat dikatakan isolasi tersebut dalam kondisi baik berdasarkan acuan standar VDE (Catalogue 228/4), pengujian pada indeks polarisasi trafo 3 jika nilainya berada pada range 1,25-2,0 maka hasil pengujian dapat dikatakan baik menurut acuan standar IEEE 62 tahun 1995, hasil pengujian tangen delta trafo 3 jika nilainya 50kV sesuai acuan pada standar IEC 60156:2018.

A transformer is a static device where a magnetic circuit and winding consisting of 2 or more windings, by electromagnetic induction, transforms the power (current and voltage) of an AC system into another system of current and voltage at the same frequency (IEC 60076 -1 of 2011). This research aims to find out the results of testing the feasibility of insulation on the transformer unit 3 of the 150kV Ancol substation, where the insulation on the transformer greatly influences the operational feasibility of the transformer. To determine the quality of the insulation of a power transformer, several test methods are used, namely testing insulation resistance, polarization index, delta tangent and breakdown voltage. This research methodology uses a quantitative method using primary data and secondary data. Primary data is obtained through the results of testing using the polarization index, delta tangent and breakdown voltage testing methods. Secondary data was obtained through literature studies which represent standards for testing polarization index, tangent delta and breakdown voltage.The test results on the insulation resistance of transformer 3 exceed 1 MΩ so it can be said that the insulation is in good condition based on the VDE standard reference (Catalogue 228/4), testing on the polarization index of transformer 3 if the value is in the range 1.25-2.0 then the results The test can be said to be good according to the 1995 IEEE 62 standard reference. If the transformer 3 tangent delta test results are 50kV according to the reference in the IEC 60156:2018 standard

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Transformator, Tahanan Isolasi, Indeks Polarisasi, Tangen Delta, Breakdown Voltage Transformator, Tahanan Isolasi, Indeks Polarisasi, Tangen Delta, Breakdown Voltage
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 05 Nov 2025 04:16
Last Modified: 05 Nov 2025 04:16
URI: https://repository.itpln.ac.id/id/eprint/3414

Actions (login required)

View Item
View Item