ANALISIS PENGGANTIAN CAPACITIVE VOLTAGE TRANSFORMER PADA BAY CIKARANG LIPPO #I GARDU INDUK 150 KV GANDAMEKAR

Salafia, Siti Masadah and Pasra, Nurmiati (2024) ANALISIS PENGGANTIAN CAPACITIVE VOLTAGE TRANSFORMER PADA BAY CIKARANG LIPPO #I GARDU INDUK 150 KV GANDAMEKAR. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 202211560 SITI MASADAH SALAFIA.pdf] Text
SKRIPSI 202211560 SITI MASADAH SALAFIA.pdf
Restricted to Registered users only

Download (6MB)

Abstract

Pada Capacitive Voltage Transformer (CVT) Bay Cikarang Lippo #1 di Gardu Induk 150 kV Gandamekar terjadi anomali hotspot dan hasil pengujian dalam pemeliharaan 2 tahunan yang buruk yang disebabkan oleh nilai tangen delta dan kapasitansi tidak memenuhi standar yang telah ditetapkan. Tujuan penelitian ini untuk mengetahui kinerja dari CVT. Metode penelitian yang digunakan bersifat kuantitatif yaitu dengan melakukan pengukuran thermovisi, pengujian pentanahan, perhitungan tahanan isolasi, tangen delta dan kapasitansi. Hasil yang didapatkan pada pengukuran thermovisi yaitu nilai T antara fasa S dan R sebesar 10,8 oC dan T antara fasa S dan T sebesar 10,6 oC. Nilai tangen delta berdasarkan hasil perhitungan untuk fasa S 4,49%. Nilai kapasitansi berdasarkan hasil perhitungan untuk fasa R 6819,5 pF, fasa S 7001,3 pF dan fasa T 6827,5 pF. Dari hasil pengukuran thermovisi, perhitungan tangen delta dan kapasitansi melebihi standar SK Dir (Surat Keputusan Direksi) No. 0520- 2.K/DIR/2014 yaitu untuk thermovisi T +10 atau <-5% rating kapsitansi. Hal tersebut menandakan adanya penurunan kertas isolasi dan sangat perlu dilakukan penggantian CVT.

At the Capacitive Voltage Transformer (CVT) Bay Cikarang Lippo #1 in the Gandamekar 150 kV Substation, a hotspot anomaly occurred, identified during the biennial maintenance due to poor results in tangent delta and capacitance values failing to meet established standards. The objective of this study is to evaluate the CVT performance. The research methodology is quantitative, involving thermovision measurements, grounding tests, insulation resistance calculations, tangent delta, and capacitance evaluations. Thermovision measurements revealed a temperature difference (ΔT) of 10.8°C between phases S and R, and 10.6°C between phases S and T. Tangent delta calculations yielded 4.49% for phase S. Capacitance calculations resulted in 6819.5 pF for phase R, 7001.3 pF for phase S, and 6827.5 pF for phase T. Based on thermovision, tangent delta, and capacitance measurements, the values exceed the SK Dir (Director's Decree) No. 0520-2.K/DIR/2014 standards: ΔT should be +10% or <-5% of rated capacitance. These findings indicate insulation paper degradation, necessitating urgent CVT replacement.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Capacitive Voltage Transformer, Pemeliharaan, Tahanan Isolasi, Tangen Delta, Kapasitansi. Capacitive Voltage Transformer, Maintenance, Insulation Resistance, Tangen Delta, Capacitance.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 05 Nov 2025 07:33
Last Modified: 05 Nov 2025 07:33
URI: https://repository.itpln.ac.id/id/eprint/3443

Actions (login required)

View Item
View Item