ANALISIS SUSUT UMUR TRAFO DAYA PADA PABRIK MAKANAN DITINJAU DARI SUHU LINGKUNGAN DAN PEMBEBANAN

Elisabeth, Fortuna Elena and Hajar, Ibnu (2024) ANALISIS SUSUT UMUR TRAFO DAYA PADA PABRIK MAKANAN DITINJAU DARI SUHU LINGKUNGAN DAN PEMBEBANAN. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 202211562 FORTUNA ELENA ELISABETH SIMATUPANG.pdf] Text
SKRIPSI 202211562 FORTUNA ELENA ELISABETH SIMATUPANG.pdf
Restricted to Registered users only

Download (5MB)

Abstract

Transformator berfungsi untuk menaikkan dan menurunkan tegangan pada sistem tenaga Listrik dengan frekuensi yang sama. Untuk memastikan transformator tetap handal dan memiliki umur panjang, penting menjaga kualitasnya, terutama terkait pembebanan dan suhu lingkungan. Transformator dirancang untuk beroperasi pada suhu lingkungan 20℃ dengan estimasi umur 20,55 tahun. Namun, pada transformator TRAFOINDO dengan suhu lingkungan 32,08℃ dan beban 100%, terjadi penurunan umur menjadi 16,51 tahun dengan susut umur 4,036 dan suhu hotspot 110,08℃. Pada beban 90%, umur transformator berkurang menjadi 19,61 tahun dengan susut umur 0,94 dan suhu hotspot 97,53℃. Sedangkan pada beban 80%, umur transformator masih sekitar 20,3 tahun dengan susut umur 0,25 dan suhu hotspot 86℃. Hal ini menunjukkan bahwa semakin tinggi suhu lingkungan dan pembebanan, semakin besar penurunan umur transformator. Untuk mengurangi dampak ini, pemeliharaan rutin sangat penting dilakukan, seperti yang diterapkan di PT. Mayora Indah Divisi Wafer Kebun Besar, Tangerang.

Transformer functions to step up and step down voltage in an electrical power system with the same frequency. To ensure that the transformer remains reliable and has a long lifespan, it is crucial to maintain its quality, especially in terms of loading and environmental temperature. Transformers are designed to operate at an ambient temperature of 20°C with an estimated lifespan of 20.55 years. However, for a TRAFOINDO transformer operating at an ambient temperature of 32.08°C and a 100% load, the lifespan decreases to 16.51 years with an aging factor of 4.036 and a hotspot temperature of 110.08°C. At 90% load, the lifespan is reduced to 19.61 years with an aging factor of 0.94 and a hotspot temperature of 97.53°C. Meanwhile, at 80% load, the transformer’s lifespan remains around 20.3 years with an aging factor of 0.25 and a hotspot temperature of 86°C. This indicates that higher environmental temperatures and loading levels lead to greater aging of the transformer. To mitigate this, routine maintenance is essential, as implemented at PT. Mayora Indah Wafer Division Kebun Besar Tangerang. Keywords: Transform

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Transformator,Pembebanan, Suhu Transformer, Load, Temperature
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 05 Nov 2025 07:45
Last Modified: 05 Nov 2025 07:45
URI: https://repository.itpln.ac.id/id/eprint/3445