ANALISA RUGI RUGI DAYA DAN JATUH TEGANGAN PADA JARINGAN DISTRIBUSI PLTA ENERGI SAKTI SENTOSA KAPASITAS 3X6 MW DAN TEGANGAN 20 KV

Manalu, Benny Kevin P and Azzahra, Septianissa (2024) ANALISA RUGI RUGI DAYA DAN JATUH TEGANGAN PADA JARINGAN DISTRIBUSI PLTA ENERGI SAKTI SENTOSA KAPASITAS 3X6 MW DAN TEGANGAN 20 KV. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 202211564 BENNY KEVIN P MANALU.pdf] Text
SKRIPSI 202211564 BENNY KEVIN P MANALU.pdf
Restricted to Registered users only

Download (6MB)

Abstract

Jaringan transmisi merupakan bagian penting Pembangkit listrik dalam menyalurkan energi listrik yang telah dibangkitkan di pusat pembangkit baik menuju gardu Induk atau menuju gardu hubung. Dalam proses penyaluran energi ini selalu terjadi rugi rugi, baik itupada rugi rugi beban yang di salurkan maupun jatuh tegangan yang di pengaruhi berbagai faktor seperti panjang saluran trasnmisi, jenis kawat penghantar, jarak antar kawat penghantar dan lain sebagainya. Analisa rugi rugi daya pada jaringan transmisi Plta Energi Sakti Sentosa menggunakan metode analisa data kuantitatif, dimana data data yang dikumpulkan pada saat proses pengumpulan data kemudian akan dihitung untuk mendapatkan berapa besarnya rugi rugi daya dan jatuh tegangan pada jaringan transmisi PLTA Energi Sakti Sentosa. Hasil dari analisa data menunjukkan bahwa rata rata rugi rugi daya dan jatuh teganganpada jaringan transmisi Plta Energi Sakti Sentosa yang terdiri dari 3 jalur transmisi yaitu Pakkat 01 sebesar 638,254 kW dengan jatuh tegangan sebesar 8,15%, Pakkat 02 sebesar 388,204 kW dengan jatuh tegangan sebesar 5,37%, dan Pakkat 03 sebesar 150,990 kWdengan jatuh tegangan sebesar 3,38%. Efisiensi pada setiap jaringan transmisi yaitu; Pakkat 01 91,85%, Pakkat 02 94,63%, Pakkat 03 96,62%.

The transmission line is an important part of power plants in distributing of electrical energy that has been generated at the generating center either to the main substation or tothe switch substation. In the process of distributing energy, losses always accure both the power losses and voltage drops which are influenced by various factor such as the lenght of the transmissiion line, the type of conductor wire, the distance beetwen the conductor wire and etc. Analysis of power losses on Energy Sakti Sentosa Hydro power plant transmissions line uses quantitative data analysis method, where the data that has been collected during the data collection process will be calculated to determine the amount of power losses and the voltage drops on Energy Sakti Sentosa hydro power plant transmission line. The result of the data analisys show that the average power losses and voltage drops onEnergy Sakti Sentosa hydro power plant transmission line which consists of 3 transmissions line, namely Pakkat 01 is 638,254 kW with a voltage drop 8,15%, Pakkat 02is 388,204 kW with voltage drop 5,37% and Pakkat 03 is 150,990 kW with voltage drop 3,38%. Efficiency in each transmissions line is; Pakkat 01 91,85%, Pakkat 02 94,63% and Pakkat 03 96,62%.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: jaringan transmisi, rugi rugi daya, efisiensi, jatuh tegangan transmissions line, power losses, efficiency, voltage drop.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 05 Nov 2025 07:45
Last Modified: 05 Nov 2025 07:45
URI: https://repository.itpln.ac.id/id/eprint/3446

Actions (login required)

View Item
View Item