Ahmad, Abel Amelia and Suyanto, Heri (2024) ANALISA PERFORMA TRANSFORMATOR BERDASARKAN PERHITUNGAN HEALTH INDEX PADA GARDU DISTRIBUSI TG413 KAPASITAS 630 KVA UP3 CIKOKOL. Diploma thesis, ITPLN.
SKRIPSI 202211568 ABEL AMELIA AHMAD.pdf
Restricted to Registered users only
Download (5MB)
Abstract
Perhitungan Health Index yang dilakukan pada trafo TG413 berdasarkan kodisinya melalui data visual insapection terdapat 3 bagian trafo yang memiliki kondisi baik yaitu kebocoran minyak, kesesuaian ampere fuse TR dan pembumian trafo sedangkan bagian trafo yang memiliki kondisi cukup yaitu kodisi fisik trafo dan kondisi liw voltage switch borad (LVSB), data load reading and profiling terdapat 1 bagian yang memiliki kondisi baik yaitu pembeanan arus TR, 2 bagian memiliki kondisi cukup yaitu ketidak seimbangan arus antar fasa dan pembebanan pada trafo, 1 bagian dalam kondisi buruk yaitu besar arus netral, data oil quality analysis terdapat 1 bagian memiliki kondisi baik yaitu suhu body trafo, 2 bagian memiliki kondisi cukup yaitu colour & appearance, 2 bagian meiliki kondisi kurang yaitu breakdown voltage dan suhu bushing TM dan 1 bagian memilki kondisi buruk yaitu bushing TR. Rekomendasi pemeliharaan yang di lakukan setelah diketahui hasil perhitungan health Index yaitu untuk bagian dengan kondisi buruk memerlukan corrective maintenance atau Tindakan segera perbaikan bahkan penggantian seperti pada besar arus netral yang memiliki presentase tinggi dengan Health Index 0 atau kondisi buruk sehingga perlu dilakukan segera penyeimbangan beban dan juga suhu pada bushing TR yang memiliki presentasi tinggi dengan Health Index 0 dan perlu dilakukan penggantian segera pada bushing TR sedangkan untuk bagian kondisi baik, cukup dan kurang direkomendasikan pemeliharaan secara periodic berdasarkan waktu pemeliharaan yang sudah ditentukan
The Health Index calculation conducted on transformer TG413 based on its condition through visual data inspection shows that 3 parts of the transformer are in good condition: oil leakage, TR ampere fuse conformity, and transformer grounding. Meanwhile, parts of the transformer in fair condition include the physical condition of the transformer and the Low Voltage Switch Board (LVSB). In terms of load reading and profiling data, 1 part shows good condition: TR current loading, 2 parts show fair condition: phase current imbalance and transformer loading, and 1 part shows poor condition: neutral current magnitude. In the oil quality analysis data, 1 part shows good condition: transformer body temperature, 2 parts show fair condition: color & appearance, 2 parts show less satisfactory condition: breakdown voltage and TM bushing temperature, and 1 part shows poor condition: TR bushing. Maintenance recommendations made after obtaining the Health Index calculation results are as follows: parts in poor condition require corrective maintenance or immediate actions such as high neutral current magnitude with a Health Index of 0, indicating poor condition, hence immediate load balancing is needed. Similarly, high temperature at TR bushing with a Health Index of 0 requires immediate replacement. For parts in good, fair, and less satisfactory conditions, periodic maintenance is recommended based on predetermined maintenance intervals.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Health Index, Pemeliharaan, Transformator Health Index, Maintenance, Transformer |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 05 Nov 2025 07:50 |
| Last Modified: | 05 Nov 2025 07:50 |
| URI: | https://repository.itpln.ac.id/id/eprint/3448 |