ANALISA DAMPAK REMBESAN MINYAK ISOLASI PADA CAPACITIVE VOLTAGE TRANSFORMER PHASA R IBT 275 KV GITET BENGKAYANG

Anggoro, Yudha Tri and Putera, Rizki Pratama (2024) ANALISA DAMPAK REMBESAN MINYAK ISOLASI PADA CAPACITIVE VOLTAGE TRANSFORMER PHASA R IBT 275 KV GITET BENGKAYANG. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 202211554 YUDHA TRI ANGGORO.pdf] Text
SKRIPSI 202211554 YUDHA TRI ANGGORO.pdf
Restricted to Registered users only

Download (6MB)

Abstract

CVT (Capacitive Voltage Transformer) memiliki komponen media isolasi diantaranya yakni minyak isolasi yang berfungsi mengisolasi bagian yang bertegangan dengan bagian yang tidak bertegangan. Pada penelitian ini ditemukan adanya rembesan pada celah penutup CVT ( Capacitive Voltage Transformer ) yang berlokasi di GITET 275 Bengkayang. Rembesan minyak ini diduga dapat menyebabkan kegagalan fungsi peralatan CVT (Capacitive Voltage Transformer ). Untuk mencegah terjadinya kerusakan atau kegagalan operasi maka perlu dilakukan sebuah analisa dan tidak lanjut yang harus dilakukan. Penelitian ini menggunakan beberapa metode penelitian yakni diantaranya metode pengumpulan data, metode analisa, dan juga metode pengolahan data. Analisa data serta pengolahan data yang dilakukan ini akan mengacu kepada sebuah standar yang digunakan yakni SKDIR 520. Pada proses penelitian ini ditemukan adanya penurunan nilai standar pada CVT (Capacitive Voltage Transformer) fasa R melalui hasil pengujian yakni pengujian tahanan isolasi, ratio serta pengujiaan tadelta dan kapasitansi. Hasil pengujian tandelta, kapasitansi, serta ratio pada fasa R berada dalam kategori tidak baik atau dibawah standar SKDIR 520 . Maka dapat disimpulkan tindak lanjut yang harus dilakukan yakni dengan cara mengganti CVT yang lama dengan yang baru.

The CVT (Capacitive Voltage Transformer) has an insulating media component, namely insulation oil, which is used to insulate the stretched part with the non-stretched part. In this study, a leakage was found in the capacitive voltage transformer (CVT) covering gap located at GITET 275 Bengkayang. This oil spill is suspected to cause the CVT equipment to fail. (Capacitive Voltage Transformer). In order to prevent the occurrence of damage or failure of the operation, it is necessary to carry out an analysis and not further that should be done. This research uses several methods of research, including data collection methods, analytical methods, and data processing methods. The data analysis and processing of this data will refer to a standard used, which is SKDIR 520. In the process of this research, it was found that there was a decrease in the standard values of the CVT (capacitive voltage transformer) phase R through the test results, which tested isolation retention, ratio, as well as tadelta and capacitance. Then it can be concluded that the follow-up to be done is to replace the old CVT with a new one.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: CVT (Capacitive Voltage Transformer), Gardu induk, minyak isolasi. CVT (Capacitive Voltage Transformer), substation, insulation oil.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 05 Nov 2025 08:03
Last Modified: 05 Nov 2025 08:03
URI: https://repository.itpln.ac.id/id/eprint/3451

Actions (login required)

View Item
View Item