SARASWATI, ANJANI and Sampurno, Sampurno (2018) KAJIAN KOORDINASI PROTEKSI TRANSFORMATOR-3 150/20 KV; 60 MVA DI GARDU INDUK CAWANG LAMA. Diploma thesis, ITPLN.
ANJANI SARASWATI (2014-11-310).pdf
Restricted to Registered users only
Download (5MB)
Abstract
Transformator daya merupakan peralatan listrik yang berfungsi untuk menyalurkan daya dengan mengubah besar tegangan. Dikarenakan fungsinya tersebut, maka transformator memiliki peranan yang sangat penting dalam sistem tenaga listrik dan harus memiliki keandalan selama beroperasi. Sehingga untuk menjaga keandalan transformator, digunakan sistem proteksi untuk melindungi transformator dari gangguan internal maupun eksternal. Sistem proteksi berfungsi untuk melindungi peralatan listrik dari gangguan yang terjadi agar peralatan tidak padam, meminimalisir daerah padam, dan waktu padam. Salah satu peralatan proteksi transformator adalah rele proteksi. Pada transformator-3 150/20 kV; 60 MVA di Gardu Induk Cawang dilindungi menggunakan lima jenis rele, yaitu rele diferensial, rele hubung tanah terbatas, rele arus lebih, rele hubung tanah, dan rele SBEF. Untuk penyetelan rele diferensial dan rele hubung tanah terbatas pada sisi 150 dan 20 kV sudah sesuai dengan SPLN yaitu minimum setting 30%. Di sisi 20 kV trafo, rele arus lebih memiliki nilai arus pick-up dan tms sebesar 1,04 A dan 0,072. Sedangkan untuk rele hubung tanah sebesar 0,173205 A dan 0,132. Untuk rele SBEF sebesar 1,7332 A dan 0,75. Di sisi 150 kV trafo, rele arus lebih memiliki nilai arus pick-up dan tms sebesar 0,924 A dan 0,168. Sedangkan untuk rele hubung tanah sebesar 0,15396 A dan 0,31.
Power transformer is an electrical device which function is to distribute electrical power and changes the value of its voltages. Therefore, transformer have an important role in the power system and needs to have reliability when it operates. This is attainable by installing protection tools to avoid the internal and external interferences. Protection system protects electrical equipments from the disturbances so that the equipments will not be damaged, also to minimize the blackout times and areas. One of transformer protection apparatus is protection relay. On 60 MVA transformer-3 150/20 kV Cawang Lama Substation is protected with five kind of relay, which are, differential relay, restricted earth fault relay, overcurrent relay, ground fault relay, and SBEF relay. On both side (HV and LV) of transformer, the setting of differential relay and restricted earth fault relay are already suitable with SPLN, which the minimum setting value is 30%. On 20 kV side of transformer, over-current relay has pick-up current and tms value are 1,04A and 0,072. While for ground fault relay are 0,173205 A and 0,132. Also for SBEF relay are 1,7332 A and 0,75. On 150 kV side of transformer, over-current relay has pick-up current and tms value are 0,924 A and 0,168. And for ground fault relay are 0,15936 A and 0,31.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Transformator, Gangguan, Sistem Proteksi, dan Koordinasi. Transformer, Faults, Protection System, and Coordination. |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 07 Nov 2025 03:09 |
| Last Modified: | 07 Nov 2025 03:09 |
| URI: | https://repository.itpln.ac.id/id/eprint/3561 |