KAJIAN DROP TEGANGAN PADA JARINGAN DISTRIBUSI TEGANGAN MENENGAH FEEDER R6 RAYON TENGGARONG

Bougari, Rivaldy Septa and Budi, Raden Panji Purnomo Willy (2019) KAJIAN DROP TEGANGAN PADA JARINGAN DISTRIBUSI TEGANGAN MENENGAH FEEDER R6 RAYON TENGGARONG. Diploma thesis, ITPLN.

[thumbnail of Rivaldy Septa Bougari (2014-11-298).pdf] Text
Rivaldy Septa Bougari (2014-11-298).pdf
Restricted to Registered users only

Download (14MB)

Abstract

Penelitian tugas akhir ini bertujuan untuk mengetahui besar nilai drop tegangan yang terjadi sepanjang JTM feeder R6 kemudian memperbaiki drop tegangannya dan menganalisis faktor-faktor yang mempengaruhi terjadinya drop tegangan di JTM feeder R6. Hasil analisa drop tegangan yang terjadi di feeder R6 dapat dijadikan pertimbangan kelayakan oleh PT PLN (Persero) Rayon Tenggarong untuk pengembangan JTM jika terjadi penambahan beban di masa yang akan datang. Metode yang digunakan dalam penelitian evaluasi drop tegangan adalah metode dokumetasi/literatur, wawancara dan observasi. Kemudian dengan metode tersebut dilakukan pengolahan data dan didapatkan hasil perhitungan drop tegangan dan faktor-faktor yang mempengaruhi adanya drop tegangan. Tegangan kirim pada feeder R6 diukur secara langsung tercatat 20.771 Volt. Berdasarkan hasil penelitian didapatkan nilai tegangan terima pada ujung feeder R6 sebesar 19537,52 Volt (5,93%) dalam kondisi beban real, 19919,99 Volt (4,1%) dengan asumsi beban gardu distribusi sebesar 60% dan 19636,35 (5,46%) dengan asumsi beban gardu distribusi sebesar 80%. Drop tegangan terjadi dikarenakan beberapa faktor, diantaranya saluran terlalu panjang, luas penampang yang kecil, nilai impedansi yang besar dan besarnya nilai beban.

This final project aims to determine the value of the voltage drop that occurs along the JTM feeder R6, then fix the voltage drop and analyze the factors that influence the occurrence of voltage drop in JTM feeder R6. The analysis of the voltage drop that occurs in the R6 feeder can be considered as a feasibility by PT PLN (Persero) Rayon Tengon for the development of JTM if there are additional burdens in the future. The method used in the voltage drop evaluation study is the documentary / literature method, interview and observation. Then with this method data processing is performed and the results of the calculation of voltage drop and the factors that influence the voltage drop are obtained. The send voltage on the R6 feeder is measured directly at 20,771 Volt. Based on the research results, the value of the received voltage at the end of the R6 feeder is 19537.52 Volt (5.93%) under real load conditions, 19919.99 Volt (4.1%) assuming the distribution of load substations is 60% and 19636,35 (5.46%) assuming the distribution of load substations is 80%. Voltage drop occurs due to several factors, including channels too long, small cross-sectional area, large impedance values and the amount of load value.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Drop tegangan, feeder R6, Jaringan Tegangan Menengah (JTM) Voltage drop, R6 feeder, Medium Voltage Network
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 07 Nov 2025 03:54
Last Modified: 07 Nov 2025 03:54
URI: https://repository.itpln.ac.id/id/eprint/3577

Actions (login required)

View Item
View Item