Denia, Velia Putri and Pramono, Tri Joko (2018) STUDI SETTING RELAY ARUS LEBIH (OCR) DAN RELAY GANGGUAN TANAH PADA PENYULANG KALIMAS DI GARDU INDUK MAMPANG BARU. Diploma thesis, ITPLN.
VELIA 201411286.pdf
Restricted to Registered users only
Download (5MB)
Abstract
Sistem distribusi tegangan menengah memiliki area yang luas dan dekat dengan pelanggan sehingga rentan terjadi gangguan-gangguan yang dapat menyebabkan terganggunya sistem distribusi. Gangguan saluran udara pada jaringan distribusi bersifat temporer dan permanen, namun sebagian besar bersifat temporer. Lebih dari 70% gangguan temporer terjadi saluran udara. Penelitian ini menggunakan metode kuantitatif. Maka dari itu digunakan proteksi PBO dan dikoordinasikan dengan rele OCR dan GFR pada incoming dan outgoing penyulang. Adapun hasil setting yang didapat di GI Duri Kosambi untuk penyulang Kursi arus hubung singkat 3 fasa OCR incoming tms=0.249, OCR outgoing tms=0.393 dan PBO tms=0.201. Pada arus hubung singkat 1 fasa ke tanah GFR incoming tms=0.319, GFR outgoing tms=0.212 dan PBO tms=0.106. Sedangkan penyulang Nikmat arus hubung singkat 3 fasa OCR incoming tms=0.295, OCR outgoing tms=0.451, PBO 1 tms=0.301 dan PBO 2 tms=0.153. Pada arus hubung singkat 1 fasa ke tanah GFR incoming tms=0.432, GFR outgoing tms=0.321, PBO 1 tms=0.213 dan PBO 2 tms=0.106.
The medium voltage distribution system has a wide area and is close to the customer so that there are susceptible to disturbances that can cause disruption to the distribution system. Air channel disruption in the distribution network is temporary and permanent, but most are temporary. More than 70% of temporary disturbances occur in the airways. This study uses quantitative methods. PBO protection is therefore used and coordinated with OCR and GFR relays on incoming and outgoing feeders. The results of the settings obtained at GI Duri Kosambi for the feeder Kursi for short-circuit current 3 phase OCR incoming tms=0.249, OCR outgoing tms=0.393 dan PBO tms=0.201. In short circuit 1 phase to ground GFR incoming tms=0.319, GFR outgoing tms=0.212 dan PBO tms=0.106. While the feeders Nikmat the short-circuit 3-phase OCR incoming tms=0.295, OCR outgoing tms=0.451, PBO 1 tms=0.301 dan PBO 2 tms=0.153. In short circuit 1 phase to ground GFR incoming tms=0.432, GFR outgoing tms=0.321, PBO 1 tms=0.213 dan PBO 2 tms=0.106.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Penutup Balik Otomatis (PBO), rele arus lebih (OCR), rele hubung tanah (GFR). Recloser, Over Current Relay (OCR), Ground Fault Relay (GFR). |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 10 Nov 2025 04:36 |
| Last Modified: | 10 Nov 2025 04:36 |
| URI: | https://repository.itpln.ac.id/id/eprint/3637 |