Paath, Son Mestizo Wellberth and Isworo, lakso (2019) ANALISA PERBAIKAN TEGANGAN DAN RUGI-RUGI PADA PENYULANG 20 KV DEPAPRE JAYAPURA. Diploma thesis, ITPLN.
cover, lembar pengesahan dan lampiran (1).pdf
Download (504kB)
BAB 1 2 3 4 5.pdf
Restricted to Registered users only
Download (1MB)
Daftar Pustaka (v).pdf
Restricted to Registered users only
Download (147kB)
Abstract
Di dalam operasi sistem distribusi nilai tegangan disetiap titik saluran harus memenuhi standar yaitu dimana tegangan (V) operasi besarnya dibatasi 0.9 Vnom ≤ V operasi ≤ 1.05 Vnom (atau +5% dan -10% Vnom) sesuai dengan SPLN No 01 Tahun 1995 yaitu + 5% dan -10 % dari tegangan nominal. Untuk penyulang di daerah Sentani Kabupaten Depapre, di Gunung Merah dijumpai jaringan tegangan menengah yang memiliki tegangan ujung jauh dibawah standar sebagai contoh Penyulang Depapre dengan panjang jaringan 68,87 km dan tegangan terima di gardu hubung Gunung Merah adalah 19 kV, yang menyebabkan terjadi jatuh tegangan sehingga perlu adanya analisa perbaikan. Terdapat metode perbaikan tegangan pada jaringan distribusi, yaitu dengan perbaikan faktor daya dengan penambahan kapasitor bank. Hasil perhitungan sebelum dilakukan perbaikan dengan menggunakan kapasitor bank tegangan terima pada ujung penyulang depapre adalah 19201,61 V dan rugi-rugi daya adalah 13051,8 Watt dengan persentase rugi daya 1,42 %. Hasil perhitungan setelah di lakukan perbaikkan dengan menempatkan kapasitor bank pada gardu distribusi STN 114 Perikanan Depapre di dapat tegangan terima adalah 19402,72 V dan rugi-rugi daya yang di dapat pada pemasangan kapasitor bank adalah 9502,562 Watt dengan persentase rugi daya 1,04 %.
In the operation of the voltage value distribution system in each channel point must meet the standard, namely where the voltage (V) operation is limited to 0.9 Vnom ≤ V operation ≤ 1.05 Vnom (or + 5% and -10% Vnom) in accordance with SPLN No. 01 of 1995 namely + 5% and -10% of nominal voltage. For feeders in the Sentani area, Depapre Regency, at Gunung Merah a medium voltage network is found that has far below standard voltage as an example Depapre Feeder with a network length of 68.87 km and the voltage received at the Gunung Merah relay station is 19 kV, which causes a voltage drop so there needs to be an improvement analysis. There is a method of repairing the voltage on the distribution network, that is by improving the power factor by adding bank capacitors. The calculation results before the repairs are carried out using a capacitor bank receiving voltage at the end of the depapre feeder is 19201.61 V and the power losses are 13051.8 Watts with a power loss percentage of 1.42%. The calculation results after being done by placing a capacitor bank on the distribution station STN 114 Fisheries Depapre received voltage is 19402.72 V and the power losses obtained at the installation of bank capacitors is 9502,562 Watts with a percentage of power loss of 1.04 %.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Jaringan Tegangan Menengah, Jatuh Tegangan, Perbaikan Tegangan, Faktor Daya. Medium Voltage Network, Voltage Drop, Voltage Improvement, Power Factor. |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 10 Nov 2025 07:40 |
| Last Modified: | 10 Nov 2025 07:40 |