Siahaan, Putra Gabriel Imanuel and Efendi, Edward (2018) ANALISIS RUGI-RUGI DAYA PADA PENGHANTAR NETRAL JARINGAN TEGANGAN RENDAH AKIBAT KETIDAKSEIMBANGAN BEBAN GARDU DISTRIBUSI KG 72 DAN KG 162 DI PT.PLN AREA TANJUNG PRIOK. Diploma thesis, ITPLN.
PUTRA GABRIEL PRINT FIX BANGET (Repaired)1 LAMPIRAN A,C,G-converted.pdf
Restricted to Registered users only
Download (1MB)
Abstract
Ketidakseimbangan beban pada sistem distribusi tenaga listrik terjadi karena penggunaan beban yang tidak merata pada tiap-tiap fasa yang berada disisi sekunder transformator. Di area Tanjung Priok merupakan penggunaan beban yang padat dengan tempat industri dan pemukiman penduduknya yang padat,sehingga waktu penggunaan beban yang tidak sama oleh tiap-tiap konsumen menyebabkan ketidakseimbangan beban. Akibat ketidakseimbangan ini akan menimbulkan arus di netral trafo. Akan tetapi akibat timbulnya arus netral di penghantar netral menyebabkan terjadinya rugi-rugi yang berdampak pada trafo yaitu rugi-rugi daya, juga mempengaruhi efisiensi transformator. Efisiensi Gardu KG 72 LWBP 99,24 % dan WBP 98,88 %, untuk Gardu KG 162 LWBP 97,85 % dan WBP 96,44 %. Dalam penelitian ini didapatkan nilai presentase ketidakseimbangan yang diambil pada luar waktu beban puncak dan waktu beban puncak pada Gardu KG 72 dan KG 162.Pada gardu KG 72 rugi-rugi kwh yang didapatkan sebesar 30,75 LWBP dan10,79 WBP untuk KG 162 LWBP 120,32 kwh ,pada WBP 35,77, dengan presentase data ketidakseimbang beban LWBP pada gardu KG 72 6% dan WBP 20,3 % dan,pada Gardu KG 162 LWBP 11,6 % dan WBP 22,6 %.Rugi-rugi penghantar netral Gardu KG 72 LWBP 1,537 kW dan WBP 2,697 kW. Untuk Gardu KG 162 LWBP 6,016 kW dan WBP 8,944 kW.
Load unbalance in the electric power distribution system occurs because the use of uneven load on each phase that is in the secondary side of the transformer. In the Tanjung Priok area is the a heavy use of loads with industrial sites and densely populated settlements, so that the time spent using unequal loads by each consumer causes a load unbalance. As a result of this unbalance will a cause currents in the neutral transformer. However, due to the emergence of neutral currents in the neutral conductor causing losses that affect the transformer. Efficiency of KG 72 LWBP substation 99.24% and 98.88% WBP, for LWBP KG 162 substation 97.85% and 96.44% WBP. In this study obtained the percentage value of the unbalance taken outside the peak load time and peak load time at 72 and KG 162. KG substations at KG substation 72 kwh losses obtained at 30.75 LWBP and 10.79 WBP for 162 LWBP KG 120.32 kwh , at WBP 35.77, with the percentage of unbalanced data the LWBP load on the 72 KG substation is 6% and WBP 20.3% and at LWBP 162 KG Substation 11.6% and 22.6% WBP. Losses in conductor neutral substation KG 72 LWBP 1,537 kW and WBP 2,697 kW . For Substation KG 162 LWBP 6,016 kW and WBP 8,944 kW.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Ketidakseimbangan beban, Rugi-rugi, Efisiensi. Load unbalance, Losses, Efficiency. |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 10 Nov 2025 08:23 |
| Last Modified: | 10 Nov 2025 08:23 |
| URI: | https://repository.itpln.ac.id/id/eprint/3670 |