Fahrezi, Zaki Setya and Pahiyanti, Novi Gusti (2025) ANALISIS PREDIKSI UMUR OPERASIONAL BATERAI 110 VOLT DC DENGAN METODE REGRESI LINEAR PADA GARDU INDUK 150 KV SEPATAN. Diploma thesis, Institut Teknologi PLN.
SKRIPSI 202011277 ZAKI SETYA FAHREZI.pdf
Restricted to Registered users only
Download (8MB)
Abstract
Baterai pada Gardu Induk memiliki fungsi utama yaitu sebagai pasokan Cadangan sistem DC ketika terjadi pemadaman total, sehingga pentingnya menjaga kinerja baterai dan masa layak pakai baterai. Pada Gardu Induk Sepatan terdapat baterai dalam unit 2 yang telah melebihi umur operasional yang direkomendasikan yaitu lebih dari 10 tahun dan baterai memiliki kondisi yang terhitung layak, sementara standar umur penggantian baterai pada Gardu Induk berkisar 20 tahun. Sehingga, dilakukan penelitian yang bertujuan untuk mengetahui perubahan kapasitas, efisiensi, dan berat jenis baterai dan untuk mengetahui umur baterai tersebut. Dengan proses discharging, metode perhitungan yang digunakan untuk menentukan masa layak pakai baterai yaitu metode regresi linear berganda. Hasil data pada tahun 2025 diperoleh efisiensi baterai terendah dibandingkan tahun yang lainnya yaitu, 65 % yang masih memenuhi batas standar PLN sesuai SKDIR 520-2 K/DIR/2014 yaitu > 60% dan masa layak baterai yaitu selama 6,6 tahun. Untuk prediksi ini dapat dijadikan pedoman perencanaan penggantian baterai yang akan datang. Agar masa layak baterai sesuai nameplate 20 tahun, perlu melakukan pemeliharaan rutin dibawah 2 tahun
The batteries in the Substation serve a primary function as a backup supply for the DC system during total blackouts, making it crucial to maintain battery performance and lifespan. At the Sepatan Substation, there is a battery in Unit 2 that has exceeded the recommended operational lifespan of over 10 years, yet it remains in a condition deemed serviceable. Meanwhile, the standard replacement lifespan for substation batteries is around 20 years. Therefore, research was conducted to determine the changes in capacity, efficiency, and specific gravity of the battery, as well as to estimate its remaining lifespan. Through the discharging process, the multiple linear regression method was used to calculate the battery's serviceable life. The data results for the year 2025 indicate the lowest battery efficiency compared to other years, at 65%, which still meets PLN's standard threshold according to SKDIR 520-2 K/DIR/2014 (> 60%), and the battery's serviceable life is projected to be 6.6 years. This prediction can serve as a guideline for future battery replacement planning. To ensure the battery lifespan aligns with the nameplate specification of 20 years, routine maintenance should be conducted at intervals of less than 2 years.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Baterai, Efisiensi, Kapasitas,Umur Battery, Efficiency, Capacity, lifespan |
| Subjects: | Bidang Keilmuan > Electrical Engineering Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Telematika Energi > S1 Sistem Informasi |
| Depositing User: | Budi Herdiansyah |
| Date Deposited: | 11 Nov 2025 02:48 |
| Last Modified: | 11 Nov 2025 02:48 |