PERBANDINGAN RUGI DAYA PADA SAMBUNGAN PENGHANTAR JARINGAN TEGANGAN MENENGAH 20 KV ANTARA PARALLEL GROOVE DAN LIVE LINE CONNECTOR DI PENYULANG GM SITUT 1 SINGKAWANG

IZZUDDIN, FEBRI and Pahiyanti, Novi Gusti (2018) PERBANDINGAN RUGI DAYA PADA SAMBUNGAN PENGHANTAR JARINGAN TEGANGAN MENENGAH 20 KV ANTARA PARALLEL GROOVE DAN LIVE LINE CONNECTOR DI PENYULANG GM SITUT 1 SINGKAWANG. Diploma thesis, ITPLN.

[thumbnail of full Skripsi bab 1 sampai 5.pdf] Text
full Skripsi bab 1 sampai 5.pdf
Restricted to Registered users only

Download (2MB)

Abstract

Untuk mendapatkan kualitas sistem pendistribusian yang optimal pada penyulang GM Situt 1 di PLN Area Singkawang dilakukan perbandingan rugi daya pada sambungan penghantar jaringan tegangan menengah 20 kV antara Parallel Groove dan Live Line Connector (LLC). Dapat di analisa dari hasil perbandingan antara kedua sambungan tersebut yang di ukur pada tiang LBS aneka sari, LBS Kirdasana dan LBS SSA pada penyulang GM Situt 1 di mana pengukuran ini dilakukan karena pada penyulang GM Situt 1 terdapat 6 titik perbaikan/pemeliharan untuk mengetahui hasil perbandingan. Analisa yang diperoleh mendapatkan kesimpulan bahwa pengukuran pada titik LBS SSA untuk Parallel Groove arus sebesar 68,1 A tegangan sebesar 18,719 kV dan cos Ø sebesar 0,911. Sedangkan pengukuran setelah menggunakan sambungan Live Line Connector (LLC) pada LBS yang sama didapat nilai arus sebesar 61,7 A, tegangan sebesar 18,987 kV dan cos Ø sebesar 0,950. Kedua sambungan ini memiliki rugi-rugi daya yang di hasilkan Parallel Groove sebesar 15,1142 kW dan Live Line Connector (LLC) sebesar 12,4967 kW untuk hasil pengukuran pada titik tiang LBS SSA, Kirdasana dan Aneka Sari. Selisih rugi daya dari hasil keseluruhan perbandingan kedua sambungan tersebut sebesar 2,6175 kW.

To get the quality of the distribution system optimal feeder GM Situt 1 in PLN Area of Singkawang done a comparison of power loss on the connection conductor of a medium voltage network 20 kV between the Parallel Groove and the Live Line Connector (LLC). Can in the analysis of the results of the comparison between the second connection such that in the measurement on the pole LBS aneka sari, LBS Kirdasana and LBS the SSA at feeders GM Situt 1 in which the measurement is performed because at the feeder GM Situt 1 there is a 6 point repairs/maintenance to determine the results of the comparison. The analysis of obtained get the conclusion that the measurement at the point of LBS the SSA for Parallel Groove flow amounted to 68,1 A voltage of 18,719 kV and cos Ø of 0,911. While the measurement after using the connection of the Live Line Connector (LLC) at the LBS the same obtained value of the current of 61,7 A, a voltage of 18,987 kV and cos Ø of 0,950. The second connection has a power loss in the produce of the Parallel Groove of 15,1142 kW and the Live Line Connector (LLC) of 12,4967 kW for the results of the measurement at the point of pole LBS SSA, Kirdasana and Aneka Sari. The difference in power loss from the overall results of the comparison of both the connection of 2,6175 kW.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Perbandingan sambungan penghantar tegangan menengah 20 kV, Live Line Connector (LLC), Parallel Groove. Comparison connection of a conductor of a medium voltage 20 kV, Live Line Connector (LLC), Parallel Groove.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 11 Nov 2025 08:19
Last Modified: 11 Nov 2025 08:19
URI: https://repository.itpln.ac.id/id/eprint/3747

Actions (login required)

View Item
View Item