Hadi, Byanta Dhaniswara and Hariyanto, Agung (2018) ANALISIS SETTING RELE DIFERENSIAL PADA TRANSFORMATOR PLTU UNIT 3 DI PT. PJB UP GRESIK. Diploma thesis, ITPLN.
Byanta Dhaniswara Hadi ( 201411155 ).pdf
Restricted to Registered users only
Download (4MB)
Abstract
Proteksi pada transformator adalah suatu bentuk perlindungan terhadap transformator guna menghindari kerusakan peralatan dan juga agar stabilitas penyaluran tenaga listrik tetap terjaga. Pembangkit Listrik Tenaga Uap pada PT. PT PJB Unit Pembangkitan Gresik yang mempunyai total daya sebesar 2255 MW, menggunakan beberapa sistem proteksi di setiap peralatan pembangkitannya. Salah satu sistem proteksi yang terdapat di transformator PLTU unit 3, yang mempunyai kapasitas 240 MVA untuk tegangan primer/ sekunder 15 kV / 154 kV, memiliki beberapa rele yang terkordinir sedemikian rupa untuk mengamankan transformator. Dari semua rele yang terdapat dalam sistem proteksi transformator, ada rele yang bekerja tidak terpengaruh setting koordinasi antar rele lainnya, yakni Rele Diferensial. Rele ini digunakan sebagai pengamanan utama dalam transformator sehingga jika terjadi gangguan pada transformator, rele ini akan langsung bekerja secara cepat dan tepat tanpa ada waktu delay untuk rele lain bekerja. Prinsip kerja rele diferensial ini adalah dengan membandingkan arus sekunder yang masuk dari CT primer ke CT sekunder harus sama dengan nol. Namun dalam kenyataan nya ada beberapa faktor yang mempengaruhi ketepatan rele diferensial ini dalam bekerja yakni, error missmatch. Error missmatch yang didapat sebesar 1,98 % yang masih dapat di tolerir dengan maksimal error missmatch sebesar 4% yang merupakan standar dari PLN. Dan setting rele yang didapat sebesar 0,84 A yang diasumsikan menjadi 0,3 atau 30% karena standar dari PLN.
Protection on the transformer is a form of protection against the transformer to avoid damage to the equipment and also so that the stability of power distribution is maintained. Steam power plant at PT. PJB UP Gresik which has a total power amounting to 2255 MW, use some protection system in every equipment of its generation. One of the protection system contained in the PLTU transformer power plant unit 3, which has a capacity of 240 MVA for the primary/secondary voltage, has several relays coordinated in such a way as to secure the transformer. All the relays contained in the protection system transformer, there is a relay that workds not affected the setting of the coordination between the relay of the other, namely differential relay. This relay is used as the primary security in the transformer so that if interference occurs on the transformer, this relay will directly work quickly and accurately without any time delay to other relay works. The working principle of differential relay this is to compare the current secondary entry of the primary CT to secondary CT must be equal to zero. But in reality, there are several factors that effect the accuracy of the differential relay in this work, namely the error mismatch. Error mismatch obtained by 1,98%, which can be tolerated with a maximum error of mismatch by 4% which is the standard of the PLN. And the relay setting is obtained by 0,94 A which is assumed to be 0,3 A or 30% because the standard of PLN
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Sistem Proteksi, Rele Diferensial, Error Missmatch Protection System, Differential Relay, Error Missmatch |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 12 Nov 2025 06:56 |
| Last Modified: | 12 Nov 2025 06:56 |
| URI: | https://repository.itpln.ac.id/id/eprint/3776 |