Abstract
Suatu transformator tenaga yang terpasang di pembangkitan merupakan sebagai peralatan yang sangat vital perannya yaitu untuk menyalurkan energi listrik ke gardu induk untuk memenuhi beban yang ada. Transformator tenaga di desain dengan suhu sekitar 20˚C namun di Indonesia transformator akan beroperasi dengan suhu sekitar 30˚C. Oleh karena itu perlu dilakukan pola pembebanannya, agar masa operasi transformator dapat digunakan lama atau minimal memenuhi standar ada. Umur pakai transformator juga dipengaruhi oleh pemanasan berlebih pada belitan akan mengakibatkan isolasi transformator menjadi rusak dan meningkatkan temperatur pada minyak sehingga akan mengubah sifat minyak transformator. Umur harap transformator dapat dicapai bila mengikuti batasan-batasan sesuai standar IEC 354 maupun SPLN 17:1979. Pada penelitian ini meneliti pengaruh pembebanan dan suhu terhadap umur transformator dengan metode yang digunakan secara kuantitatif yang dijabarkan secara deskriptif sehingga permasalahan diatas berupa angka-angka. Dari hasil perhitungan yang telah dilakukan berdasarkan rumus pada standar IEC 354, bahwa pembebanan PLTA Timo konstan sebesar 80% sehingga mengakibatkan susut umur minimal 34% dengan perkiraan umur selama 54,56 tahun.
A power transformer installed on a power generation unit is a vital equipment whoserole is to distribute electrical energy to substation to meet the load demand. Power transformer is designed with a working temperature of 20˚C, however in Indonesia power transformer operates with temperature around 30˚C. Therefore, loading scheme needs to be done, in order for the transformer operating period to able to work for a long time or at least tocomply with the standards. Service duration of a transformer is also affected by excessive heating of the coil, which in turn causing transformer's isolation to decay and raising the oil temperature that cause a change in the oil characteristic. If this change persists for a significant amount of time, it will lower the isolation grade of the oil. This thesis researches the effects of load given to power transformer and the effect of temperature on power transformer lifetime shrinkage with the method used is quantitative and then further elaborated descriptively, therefore the problems mentioned earlier are described as number figures. From the calculations, the loading of PLTA Timo is constant amounting to 80%, hence causing lifetime shrinkage of 34% minimum with lifetime estimation of 54,56 years.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | transformator, umur, suhu, pembebanan. transformer, lifetime, temperature, load. |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 12 Nov 2025 07:38 |
| Last Modified: | 12 Nov 2025 07:38 |
| URI: | https://repository.itpln.ac.id/id/eprint/3787 |