KAJIAN KAPASITAS PEMUTUS TENAGA (PMT) SISI 20 KV PADA GARDU INDUK NEW BINTARO

Hasim, Fergya Sugandhi and Willy, Purnomo (2019) KAJIAN KAPASITAS PEMUTUS TENAGA (PMT) SISI 20 KV PADA GARDU INDUK NEW BINTARO. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI Fergya (2014-11-130).pdf] Text
SKRIPSI Fergya (2014-11-130).pdf
Restricted to Registered users only

Download (1MB)
[thumbnail of Lembar Bimbingan Skripsi.pdf] Text
Lembar Bimbingan Skripsi.pdf

Download (806kB)
[thumbnail of Pernyataan Keaslian Skripsi.pdf] Text
Pernyataan Keaslian Skripsi.pdf

Download (653kB)
[thumbnail of Lembar Pengesahan Tim Penguji.pdf] Text
Lembar Pengesahan Tim Penguji.pdf

Download (570kB)
[thumbnail of Lembar Pengesahan Skripsi.pdf] Text
Lembar Pengesahan Skripsi.pdf

Download (497kB)
[thumbnail of LAMPIRAN.pdf] Text
LAMPIRAN.pdf

Download (1MB)

Abstract

Dibangunya gardu induk baru di bintaro memiliki peran penting dalam memenuhi kebutuhan energi listrik untuk konsumen. Suntuk mengatasi gangguan yang terjadi, maka dipasang system pengaman. Dalam sistem pengaman terdapat pemutus tenaga (PMT) atau Circuit Breaker (CB) yang merupakan saklar mekanis, yang mampu menutup, mengalirkan dan memutus arus beban dalam kondisi normal maupun memutuskan dalam kondisi gangguan seperti kondisi hubung singkat. Diibutuhkan kapasitas rating PMT yang sesuai agar pengiriman energi listrik menjadi lebih andal. Hasil perhitungan manual rating breaking capacity PMT menunjukan bahwa nilai arus gangguan hubung singkat untuk penyulang sebesar 10,297 kA, untuk arus gangguan pada Busbar 20 kV sebesar 11,463 kA, dan untuk transformator sebesar 5,985 kA. Pada perhitungan menggunakan ETAP menunjukan bahwa nilai arus gangguan hubung singkat untuk penyulang sebesar 10,259 kA, untuk arus gangguan pada Busbar 20 kV sebesar 11,128 kA, dan untuk transformator sebesar 5,017 kA. Pemilihan rating PMT yang terpasang sudah sesuai berdasarkan perhitungan arus gangguan hubung singkat. Sehingga dapat disimpulkan pemutus tenaga (PMT) Gardu Induk New Bintaro sisi 20 kV sudah memenuhi syarat dan sesuai dengan kebutuhan.

The construction of a new substation in bintaro has an important role in meeting the electricity needs of consumers. To overcome the disturbances that occur, the security system is installed. In the safety system there is a power breaker (PMT) or Circuit Breaker (CB) which is a mechanical switch, which is able to close, drain and disconnect the load current under normal conditions and decide in disturbance conditions such as short circuit conditions. The appropriate PMT rating capacity is needed so that electrical energy shipments become more reliable. The results of manual rating breaking capacity PMT show that the value of short circuit fault for feeder is 10.297 kA, for fault currents in Busbar 20 kV at 11.463 kA, and for transformers at 5.985 kA. The calculation using ETAP shows that the value of short circuit fault for feeder is 10.259 kA, for fault currents in Busbar 20 kV at 11.128 kA, and for transformers at 5.017 kA. Selection of the installed PMT rating is appropriate based on the calculation of short circuit fault current. So it can be concluded that the power breaker (PMT) on the 20 kV New Bintaro Substation has fulfilled the requirements and according to needs.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: PMT, CB, Distribusi, Breaking Capacity. PMT, CB, Distribution, Breaking Capacity.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 12 Nov 2025 08:17
Last Modified: 12 Nov 2025 08:17
URI: https://repository.itpln.ac.id/id/eprint/3789

Actions (login required)

View Item
View Item