ANALISIS KEHANDALAN TRANSFORMATOR DAYA 60 MVA MENGGUNAKAN METODE DISTRIBUSI WEIBULL DAN PENGUJIAN TANGEN DELTA

Setyawan, Muhammad Yunus Anis and Pujotomo, Isworo (2018) ANALISIS KEHANDALAN TRANSFORMATOR DAYA 60 MVA MENGGUNAKAN METODE DISTRIBUSI WEIBULL DAN PENGUJIAN TANGEN DELTA. Diploma thesis, ITPLN.

[thumbnail of Analisis Kehandalan Transformator Daya 60 MVA Menggunakan Distribusi Weibull dan Pengujian Tangen Delta.pdf] Text
Analisis Kehandalan Transformator Daya 60 MVA Menggunakan Distribusi Weibull dan Pengujian Tangen Delta.pdf
Restricted to Registered users only

Download (6MB)

Abstract

Kehandalan merupakan kemampuan sistem atau komponen untuk bekerja sesuai fungsi yang dibutuhkan dalam kondisi tertentu dan dalam rentang waktu yang spesifik. Skripsi ini membahas tentang analisis kehandalan transformator daya berdasarkan nilai dari laju kegagalan dan nilai fungsi kehandalanya. Untuk mempertahankan keandalan, asal kegagalan dan tingkat kegagalan serta penyebab kerusakan fisik harus di analisis dan dipelajari. Distribusi Weibull telah banyak digunakan sebagai metode matematika untuk menentukan laju kegagalan, kehandalan dan memprediksi sisa umur peralatan apapun. Dengan dilakukan perhitungan didapat nilai MTTF (mean time to failure) transformator daya 4 GI Cengkareng PT. PLN adalah 3,8103 tahun, laju kegagalan pertahunnya 0,4027% dan nilai kehandalanya adalah 0,3614. Nilai kehandalan tersebut dikatakan kurang handal karena jauh dari nilai probabilitas sangat handal yang bernilai 1. Maka dari itu perlu pengujian-pengujian lebih lanjut untuk menggambarkan kondisi transformator lebih spesifik. Salah satu pengujianya adalah uji tan ẟ yang merupakan metode diagnostik secara elektrikal untuk mengetahui kondisi isolasi transformator. Data hasil uji dianalisa dengan membandingkan nilai tangen delta dengan standar ANSI C 57.12.90 dan diperoleh bahwa isolasi pada sisi tersier voltage dengan mode pengujian CTG+CHT adalah 2,15% dan mode pengujian CTG adalah 2,20%, nilainya lebih dari standar yang diizinkan yaitu lebih dari 1% maka dari itu kondisi isolasi perlu diwaspadai dalam keadaan buruk

Reliability is the ability of the system or component to work according to the required function under certain conditions and within a specific time. This research discusses the reliability analysis of power transformers based on the value of the failure rate and the value of its destructive function. To maintain reliability, the origin of failure and failure rates and causes of physical damage should be analyzed and studied. Weibull distribution has been widely used as a mathematical method to determine failure rates, reliability and predict the remaining life of any equipment. With the calculation obtained MTTF value (mean time to failure) power transformer 4 GI Cengkareng PT. PLN is 3.8103 years, the annual rate of failure is 0.4027% and its value is 0.3614. The reliability value is said to be less reliable because far from the value of probability is very reliable which is worth 1. Therefore than need further tests to describe the condition of the transformer more specific. One of the tests is the tan ẟ test which is an electrical diagnostic method to determine the condition of the transformer isolation. The result of data testing were analyzed by comparing the tan ẟ value with ANSI C standard 57.12.90 and it was found that the isolation on the tertiary voltage side with the CTG + CHT testing mode was 2.15% and the CTG testing mode was 2.20%, more than the standard permitted more than 1% therefore isolation conditions need to be watched out in bad circumstances.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Transformator daya, Kehandalan, Distribusi Weibul, Tangen delta Power Transformer, Reliability, Weibull Distribution, tan ẟ
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 12 Nov 2025 12:40
Last Modified: 12 Nov 2025 12:40
URI: https://repository.itpln.ac.id/id/eprint/3795

Actions (login required)

View Item
View Item