trikusuma, Muhammad Umar and SIREGAR, MASBAH R T (2018) STUDI PERBANDINGAN TINGGI DUDUKAN STRUKTUR PANEL SURYA TERHADAP PENGARUH EFFISIENSI DAYA DI PLTS GILI TRAWANGAN 400 kWp. Diploma thesis, ITPLN.
Skripsi Muhammad Umar Trikusuma(2014-11-124.pdf
Restricted to Registered users only
Download (3MB)
Abstract
Studi ini dilaksanakan setelah PT. PLN (Persero) Sektor Lombok PL Tanjung melakukan analisa penyebab menurunnya kinerja PLTS Gili trawangan 400 kWp. Salah satu solusi untuk meningkatkan kinerja ialah dengan meningkatkan ketinggian struktur kedudukan panel agar sirkulasi udara menjadi baik, terhindar dari bayangan pepohonan atau bangunan tinggi sekitar, dan dapat meningkat daya keluaran. Pada Panel Surya dengan struktur kedudukan ditinggikan (string 5.9 dan 5.) memiliki tinggi I sebesar 2 meter dan Tinggi II 1,3 meter sedangkan pada panel surya dengan strukur kedudukan belum ditinggikan (string 3.7 dan 3.9) memiliki tinggi I sebesar 1,5 meter dan Tinggi II sebesar 0.9 meter. Dimana dalam satu string terdapat 16 panel surya yang dirangkai seri yang memiliki daya 180 Wp. Efisiensi pada nameplat adalah 14.5% pada jam 16.00 tanggal 25 Maret 2018 efisiensi sel surya mendekati efisiensi pada nameplat dengan efisiensi terbesar pada string 5.9 yaitu 12.1494%. itu dikarenakan banyak hal salah satunya pengaruh suhu pada panel. Perbandingan selisih efisiensi daya rata-rata ∆ɲ antara string 5.9 dan string 3.7 adalah 0.68552% pada tanggal 24 Maret 2018 dan pada tanggal 25 Maret 2018 rata-rata ∆ɲ adalah 0.67437%. Jadi dengan perbedaan ketinggian kedudukan panel surya pada tinggi I 50 cm dan tinggi II 40 cm dapat meningkatkan efisien daya sekitar 0.6-0.7%.
The study was carried out after PT. PLN (Persero) Sector Lombok PL Tanjung perform analysis of the causes of the declining performance of SPP Gili trawangan 400 kWp. One solution to improve performance is to increase the height of the structure to position the panel so that air circulation becomes better, spared from the shadow of the trees or high buildings around, and can increase power output. On the Solar Panel with the structure of the position of the elevated (string 5.9 and 5.) have a high of 1 by 2 meters High and 2 1.3 meters while the solar panel to the structure of the position has not yet elevated (string 3.7 and 3.9) has a height of 1 by 1.5 meters High and 2 by 0.9 meters. Where in one string there are 16 solar panels which are strung together series which has a power of 180 Wp. Efficiency on the nameplat is 14.5% at 16: 00 hours March 25, 2018 the efficiency of solar cells approach efficiency on the nameplat with the greatest efficiency on the string of 5.9 that is 12.1494%. it's because a lot of things one of them is the influence of the temperature on the panel. A comparison of the difference in the efficiency of the average power ∆ɲ between the string of 5.9 and strings 3.7 is 0.68552% on March 24, 2018 and on March 25, 2018 the average ∆ɲ is 0.67437%. So with a height difference of the position of the solar panels on the high I 50 cm and a height of II to 40 cm can improve the efficient power of about 0.6-0.7%.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Efisiensi, PLTS, Ketinggian, struktur, perbandingan heigt, structur, comparative , Solar Power Plant, efficiency |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 12 Nov 2025 13:09 |
| Last Modified: | 12 Nov 2025 13:09 |
| URI: | https://repository.itpln.ac.id/id/eprint/3800 |