Sabarta, Nizuar and Sudibyo, Uno Bintang (2018) PENGARUH KETIDAKSEIMBANGAN BEBAN TERHADAP RUGIRUGI PADA PENGHANTAR NETRAL DAN EFISIENSI TRANSFORMATOR GARDU DISTRIBUSI LA017 PT. PLN AREA LAH. Diploma thesis, ITPLN.
Wisam Prima Nugraha (201411106).pdf
Restricted to Registered users only
Download (1MB)
Lampiran.pdf
Download (263kB)
Abstract
Ketidakseimbangan beban pada trafo distribusi tenaga listrik selalu terjadi dan ketidakseimbangan tersebut terjadi karena ketidaksamaan pemakaian energi listrik. Akibat ketidakseimbangan beban tersebut mengalir arus di netral trafo. Arus yang mengalir di penghantar netral trafo ini menyebabkan terjadinya rugirugi, yaitu rugi-rugi akibat adanya arus netral pada penghantar netral trafo dan rugi-rugi akibat arus netral yang mengalir ke tanah. Dalam menganalisis masalah menggunakan model matematis meliputi persamaan ketidak seimbangan beban trafo, rugi-rugi daya dan efisiensi. Setelah dianalisis menunjukkan bahwa trafo dalam keadaan tidak seimbang dimana bila terjadi ketidakseimbangan beban yang besar, maka arus netral yang muncul juga besar. Efisiensi trafo akan semakin besar jika selisih daya masuk dan daya keluar kecil. Rugi daya akibat adanya arus netral pada penghantar netral (PN) yang terjadi 0,906 kW, rugi akibat arus netral yang mengalir ke tanah (PG) sebesar 6,350 kW, dan efisiensi 93,86%.
The unbalanced load in electric power distribution transformer always happen and it is caused by unsame weared energy. The effect of the unbalanced load is appear as a neutral current. These neutral current cause losses, those are losses caused by neutral current in neutral conductor on distribution transformers and losses caused by neutral current flows to ground. In analysing used model mathematical the problem covering equation unbalanced load, losses and efficiency. In conclusion, when high unbalanced load happened, then the neutral current that appear is also high, ultimately the losses that caused by the neutral current flows to ground will be high too. Transformer efficiency increases depending on whether the difference between power input and output is minor. Power losses caused by neutral current in neutral conductor (PN) is 0,906 kW, losses that caused by the neutral current flows to ground (PG) is 6,350 kW, and efficiency is 93,86%.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Ketidakseimbangan Beban, Arus Netral, rugi-rugi, Efisiensi. Unbalanced Load, Neutral Current, Losses, efficiency. |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 13 Nov 2025 06:54 |
| Last Modified: | 13 Nov 2025 06:54 |
| URI: | https://repository.itpln.ac.id/id/eprint/3825 |