ANALISIS PENGARUH GAS TERLARUT DALAM MINYAK TRANSFORMATOR TERHADAP KONDISI TRANSFORMATOR DENGAN METODE DISSOLVED GAS ANALYSIS (DGA)

Hakim, Kamil Faishal and Pujotomo, Isworo (2018) ANALISIS PENGARUH GAS TERLARUT DALAM MINYAK TRANSFORMATOR TERHADAP KONDISI TRANSFORMATOR DENGAN METODE DISSOLVED GAS ANALYSIS (DGA). Diploma thesis, ITPLN.

[thumbnail of analisis pengaruh gas terlarut dalam minyak transformator terhadap kondisitransformator dengan metode dga.pdf] Text
analisis pengaruh gas terlarut dalam minyak transformator terhadap kondisitransformator dengan metode dga.pdf
Restricted to Registered users only

Download (2MB)

Abstract

PLTGU Muara karang adalah salah satu pembangkit yang mensuplai tempat dengan pelanggan VVIP. Oleh sebab itu keandalan sistem tenaga listrik PLTGU Muara Karang harus terjaga. Salah satu peralatan penting penunjang keandalan sistem tenaga listrik PLTGU Muara Karang adalah transformator. Fungsi transformator sangat vital yaitu berfungsi untuk menyalurkan tenaga listrik dari tegangan tinggi ke tegangan rendah ataupun sebaliknya. Untuk mengetahui kondisi serta menjaga keandalan transformator dapat di lakukan dengan menguji minyak transformator dengan metode Dissolved Gas Analysis (DGA). Dengan metode DGA minyak di ekstraksi dan di pisahkan gas yang terlarut didalam nya. Gas tersebut di analisis menggunakan teknik total dissolved combustible gas(tdcg) dan key gas. Dari analisis tdcg di ketahui kondisi transformator GTG 1 berada pada kondisi 2 dengan nilai tdcg 806 ppm dan TDCGv sebesar 32.24 liter. Kondisi 2 menandakan gas individu sudah mulai meningkat dan perlu di waspadai. Dari metode gas kunci trafo terindikasi mengalami overheating selulosa karena kandungan gas karbon monoksida dominan sebesar 71.091% dengan nilai 573 ppm. Untuk nilai tegangan tembus pada transfrormator di dapatkan 53.8 kV dalam hal ini kondisi tegangan tembus masuk dalam kategori baik apabila mengacu pada IEC 156-60422 / 2005.

PLTGU Muara Karang is one of the plants that supply places with VVIP customers. Therefore, the reliability of the Muara Karang power plant system must be maintained. One of the important tools supporting the reliability of the Muara Karang PLTGU power system is a transformer. The function of the transformer is very vital, which functions to deliver electricity from high voltage to low voltage or vice versa. To determine the condition and maintain the reliability of the transformer can be done by testing the transformer oil with the Dissolved Gas Analysis (DGA) method. With the DGA method the oil is extracted and separated by the dissolved gas in it. The gas is analyzed using total dissolved combustible gas (TDCG) and gas key techniques. From the tdcg analysis, the condition of the GTG 1 transformer is in condition 2 with 806 ppm tdcg and 32.24 liters of TDCGv. Condition 2 indicates that individual gas has begun to increase and needs to be alerted. The transformer lock gas method indicated cellulose overheating because the dominant carbon monoxide gas content was 71,091% with a value of 573 ppm. For the translucent voltage value on the transfrormator, it gets 53.8 kV in this case the breakdown voltage condition is in good category when referring to IEC 156-60422 / 2005.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Dissolve Gas Analysis (DGA), minyak transformator, overheating selulosa Dissolve Gas Analysis (DGA), transformer oil, cellulose overheating
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 15 Nov 2025 12:30
Last Modified: 15 Nov 2025 12:30
URI: https://repository.itpln.ac.id/id/eprint/3883

Actions (login required)

View Item
View Item