Pada jaringan tegangan rendah merupakan titik akhir dari pendistribusian listrik dari pembangkit kepada konsumen, sehingga potret pelayanan dapat dilihat dari mutu tegangan dan tingkat keandalan dari sisi tegangan rendah. Apabila tegangan di sisi tegangan rendah sudah sesuai dengan standar PLN maka bisa dikatakan kualitas tegangan sistem sudah baik. Tapi pada kenyataan masih banyak di temukan beberapa daerah yang masih memiliki jatuh tegangan pada sisi tegangan rendah yang membuat pelanggan hanya dapat menikmati listrik dengan tegangan kurang dari 231 Volt dan tentu saja permasalahan jatuh tegangan ini sanggat merugikan pelanggan karena dapat merusak peralatan listrik yang dimiliki oleh pelanggan. Untuk mengatasi jatuh tegangan ini maka dilakukanlah penambahan trafo sisipan yang digunakan supaya tegangan yang di terima konsumen sesuai dengan SPLN 1 tahun 1995 yaitu 231 Volt (+ 5%, - 10%). Dari hasil perhitungan jatuh tegangan dan running ETAP pada saat beban puncak di gardu tiang B4-F/116 didapatkan nilai jatuh tegangan pada perhitungan sebesar 15,47% dan hasil running ETAP sebesar 88,3% nilai ini sudah melebihi standar PLN. Selain itu pada gardu tiang B4-F/116 ini trafo yang dipakai pembebanan trafonya 202,7% yang seharusnya trafo dibebani hanya 80%. Upaya untuk memperbaiki jatuh tegangan pada gardu tiang B4-F/116 adalah dengan pecah beban dan penambahan trafo. Jatuh tegangan yang terjadi setelah perbaikan tegangan dengan pecah beban dan penambahan trafo sebesar 93,5%. Jatuh tegangan yang baru sudah memnuhi standar dan trafo yang dipakai pembebanan sudah dibawah 80%.

On the low voltage network is an end point of the distribution of electricity from plants to consumers, so that the portrait service can be seen from the quality of voltage and level of reliability of the low voltage side. If the voltage on the low voltage side are in accordance with PLN standards it can be said that the quality of the system voltage is good. But in reality many still find some areas which still has a falling voltage on the low voltage side which makes customer can only enjoy the electricity with a voltage less than 231 Volt and of course the problems of the voltage drop across this was very detrimental to customers because it can damage the electrical equipment owned by the customer. To cope with the fall in this voltage then perform the addition of the transformer inserts are used so that the voltage at the consumers in accordance with SPLN 1 1995 i.e. 231 Volts (+ 5%, -10%). From the results of the calculation of the voltage drop and running the ETAP at the time of peak load on the substation pole B4-F/116 the obtained value of the voltage drop on the calculation of of 15.47% and the results of running the ETAP by of 88.3% this value already exceeds the standard PLN. In addition, on the substation pole B4-F/116 this transformer used transformer loading 202,7% should the transformer be burdened only 80%. Efforts to fix the voltage drop on the substation pole B4-F/116 is the rupture load and the addition of a transformer. The voltage drop that occurs after the improvement of the voltage with the rupture load and the addition of transformers amounting to 93,5%. The voltage drop that new already comply with the standard and transformer used loading is already below 80%.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Jaringan Tegangan Rendah, Jatuh Tegangan, Pecah Beban Low Voltage Network, the Voltage drop, Rupture Load
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 20 Nov 2025 14:07
Last Modified: 20 Nov 2025 14:07
URI: https://repository.itpln.ac.id/id/eprint/3985

Actions (login required)

View Item
View Item