EVALUASI DROP TEGANGAN PADA JARINGAN TEGANGAN MENENGAH 20 KV PENYULANG GANDUM PT.PLN (PERSERO) AREA BANDENGAN

Fatimah, Fatimah and Pramono, Tri Joko (2017) EVALUASI DROP TEGANGAN PADA JARINGAN TEGANGAN MENENGAH 20 KV PENYULANG GANDUM PT.PLN (PERSERO) AREA BANDENGAN. Diploma thesis, ITPLN.

[thumbnail of Laporan Skripsi.pdf] Text
Laporan Skripsi.pdf
Restricted to Registered users only

Download (1MB)
[thumbnail of Lembar Lampiran 1.pdf] Text
Lembar Lampiran 1.pdf

Download (723kB)
[thumbnail of Lembar Lampiran 2.pdf] Text
Lembar Lampiran 2.pdf

Download (128kB)

Abstract

Sistem distribusi sangat penting dalam penyaluran tenaga listrik ke beban, maka sistem distribusi yang baik dan efisien sangat diperlukan. Faktor yang bisa menyebabkan kurang baiknya sistem distribusi tenaga listrik adalah besarnya nilai jatuh tegangan dalam sistem distribusi yang telah ada. Dalam distribusi tenaga listrik digunakan jaringan tegangan menengah 20 kv dan tegangan rendah 380 /220 V. Sistem distribusi di Gardu Induk Angke Penyulang Gandum menggunakan jaringan tegangan menengah dengan saluran kabel bawah tanah. Hal ini digunakan karena banyaknya bangunan yang menjulang tinggi serta padatnya penduduk pada daerah tersebut. Dan diketahui bahwa semakin panjang saluran serta arus beban yang digunakan maka akan semakin besar nilai jatuh tegangan. Dari hasil perhitungan jatuh tegangan pada Penyulang Gandum di Gardu Induk Angke menggunakan perhitungan manual dan perhitungan dengan simulasi program ETAP 12.6.0 menunjukan perbedaan hasil yang sedikit. Hasil jatuh tegangan yang di dapat dari perhitungan manual paling besar dengan nilai persentase tegangan 1,94%, sedangkan untuk hasil yang di dapat menggunakan program ETAP 12.6.0 paling besar dengan nilai persentase tegangan 2,01%. Ini masih dalam standar PLN karena belum melebihi standar yang ditentukan yaitu sebesar -10% dari tegangan nominalnya.

Distribution system is very important in the distribution of electric power to the load. Therefore, a good and efficient distribution system is needed. The underlying cause of poor electric power distribution system is the amount of voltage drop values in the existing system. In the electric power distribution, 20 kV mediumvoltage and 380/220V low voltage networks are used. The distribution system of Gandum Feeder in Angke Substation uses medium-voltage network with Underground Cable channel. They are used because of the towering buildings and the dense population in the area. It is known that the longest the channel and the load current are, the greater the voltage drop. From the result of the voltage drop calculation of Feeder Gandum in Angke Substation, which uses manual calculation and ETAP 12.6.0 program, it showed a slight difference in the result. The result of the voltage drop obtained from manual calculation showed that the percentage value of voltage is 1.94%, while the result obtained from ETAP 12.6.0 program showed that the percentage value is 2.01% These results are still in the PLN standard, because it has not exceeded the specified standard that is -10% of its nominal voltage.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Jatuh Tegangan, ETAP 12.6, Panjang Saluran, 1,94%, 2,01%. Voltage Drop, ETAP 12.6, Channel Length, 1.94%, 2,01%.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro