Abstract

Di dalam operasi sistem distribusi nilai tegangan di setiap titik saluran harus memenuhi standar mutu tegangan yaitu dimana tegangan (V) operasi besarnya dibatasi 0.9 Vnom ≤ V operasi ≤ 1.05 Vnom (atau +5% dan -10% Vnom) sesuai dengan SPLN No 01 Tahun 1995 yaitu + 5% dan -10 % dari tegangan nominal. Untuk beberapa penyulang di daerah Lampung Kabupaten Tulang Bawang, Menggala masih dijumpai beberapa Jaringan Tegangan Menengah (JTM) yang memiliki tegangan ujung jauh dibawah standar sebagai contoh Penyulang Pakis di Gardu Induk Menggala. Penyulang Pakis memiliki panjang jaringan 289 km dan tegangan ujung sebesar 13.81 kV. Dikarenakan terjadi jatuh tegangan yang besar sehingga perlu adanya perbaikan. Ada beberapa cara perbaikan tegangan pada JTM distribusi, dalam melakukan perbaikan harus disesuaikan dengan kondisi jaringan secara fisik maupun operasinya. Sehubungan penyulang Pakis memiliki panjang jaringan sangat panjang dan daya beban yang cukup besar maka dalam pembahasan skripsi digunakan 2 metode perbaikan tegangan yaitu menggunakan metode pemotongan saluran beban dan sisa beban saluran yang dipotong akan dipikul dengan penambahan gardu induk mini. Sehingga tegangan yang di dapat sesuai standar yang ditetapkan.

In the operation of the distribution system the voltage values at each point of the line must meet the quality standard of voltage where the voltage (V) operation is limited to 0.9 Vnom ≤ V operation ≤ 1.05 Vnom (or + 5% and -10% Vnom) in accordance with SPLN No. 01 Year 1995 ie + 5% and -10% of nominal voltage. For some feeder’s in the Lampung area of Tulang Bawang Regency, Menggala still encountered some Medium Voltage Networks which have far lower end voltage as an example of Pakis Feeder in Menggala main substation .Pakis feeder has a network length of 289 km and a tip end of 13.81 kV. Due to the large drop voltage so that need to be repaired. There are several ways of fixing voltage on JTM distribution, in doing the repair must be adjusted to the condition of the network physically and its operation. In relation to Pakis Feeder has a very long network length and load power is large enough in the discussion of the thesis used 2 methods of voltage corrective that is using the method of cutting the load channel and the remaining load of the cut channel will be borne with the addition of mini main substations. So that the voltage in the can according to the standard set

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Jaringan Tegangan Menengah, Jatuh Tegangan, Perbaikan Tegangan Penyulang. Medium Voltage Networks ,Drop Voltage, Corrective On Feeder Voltage
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 01 Dec 2025 03:41
Last Modified: 01 Dec 2025 03:41
URI: https://repository.itpln.ac.id/id/eprint/4248

Actions (login required)

View Item
View Item