Bhiswara, Ulung and Paryoto, Djoko (2017) Analisis Perbaikan Mutu Tegangan Akibat Voltage Drop pada Jaringan Tegangan Rendah dengan Metode Pecah Beban pada Gardu CNK3 Area Ciputat. Diploma thesis, ITPLN.
1.Cover.pdf
Download (111kB)
2.Opening.pdf
Download (1MB)
3.BAB I.pdf
Download (603kB)
4.BAB II.pdf
Download (2MB)
5.BAB III.pdf
Restricted to Registered users only
Download (650kB)
6.BAB IV.pdf
Restricted to Registered users only
Download (2MB)
7.BAB V .pdf
Restricted to Registered users only
Download (253kB)
8.Daftar Pustaka.pdf
Download (164kB)
9. Daftar Riwayat Hidup.pdf
Download (148kB)
Abstract
Analisa ini didasarkan pada kebutuhan untuk perbaikan profil tegangan pada jaringan tegangan rendah pada gardu CNK3 di Area Ciputat yang mengalami drop tegangan dan terlalu tingginya pembebanan pada trafo. Metode yang dipilih untuk memperbaiki profil tegangan adalah metode pecah beban yang dilakukan dengan cara mengurangi beban pada jurusan B pada gardu CNK3 dan dipindah ke jurusan A pada gardu CNK18. Dengan dibuatnya analisa ini diketahui bahwa losses transformator berkurang dari 11.624 kWh menjadi 6.149 kWh, losses pada jaringan berkurang dari 14.616 kWh menjadi 11.624 kWh, dan voltage drop pada gardu CNK3 menurun, selain itu diketahui bahwa kerugian pln dengan periode penggunaan gardu selama 2.169,55 jam pertahun mencapai 20.056.250 rupiah, dan dengan biaya investasi pecah beban sebesar 27.767.000 rupiah payback period akan terjadi setelah 1,38 tahun.
This analysis based on the need for improvement of voltage profile on low voltage system at CNK3 substation in Ciputat Area which experienced voltage drop and high load transformer. The method chosen to improve the voltage profile is the load breakdown method which is done by reducing the load on some of B feeder at the CNK3 substation and transfer it to A feeder on the CNK18 substation. By making this analysis it is known that transformer losses decreased from 11,624 kWh to 6,149 kWh, system losses decreased from 14,616 kWh to 11,624 kWh and the voltage drop on the CNK3 substation also decreased, it was known that the PLN losses with the use of substation for 2,169.55 hours per year reached 20,056,250 rupiah, and with 27,767,000 rupiah of investment, PLN payback period will occur after 1.38 years.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Voltage Drop, Rugi Jaringan, Rugi Transformator, Investasi, Payback Period, Pecah Beban Voltage Drop, System Losses, Transformer Losses, Investment, Payback Period, Load Breakdown |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 02 Dec 2025 05:29 |
| Last Modified: | 02 Dec 2025 05:29 |
| URI: | https://repository.itpln.ac.id/id/eprint/4304 |