Transformator tenaga merupakan alat yang vital dalam fungsinya menyalurkan daya ke pusat beban. Pada Transformator tenaga tidak dapat dihindari adanya gangguan. Salah satu gangguannya adalah gangguan hubung singkat yang secepatnya harus diatasi. Oleh karena itu untuk mengatasi gangguan tersebut agar tidak menimbulkan kerusakan diperlukan sistem proteksi yang memenuhi persyaratan sensitifitas, dapat dipercaya, selektifitas, dan kecepatan, yang semuanya bergantung pada ketepatan seting peralatan proteksinya. Peralatan proteksi yang biasa digunakan untuk tansformator daya adalah rele diferensial dan rele arus lebih yang berfungsi mengintruksikan PMT untuk membuka kontak-kontaknya, sehingga transformator tenaga yang terganggu dapat dipisahkan dari sistem. Dari analisa hasil pengujian rele arus lebih didapati TMS 0,27 disisi 150 kV serta 0,39 disisi 20 kV dan dari analisa perhitungan yang dilakukan diperoleh TMS 0,614 disisi 150 kV serta 0,1799 disisi 20 kV. Berdasarkan analisa tersebut, setting rele arus lebih yang terpasang sudah tepat dan handal terhadap gangguan eksternal. Dan dari analisa yang dilakukan terhadap rele diferensial maka didapati rele diferensial sensitif terhadap gangguan internal.

Power transformers is a vital tool in its function to supply power to the load center . In the power transformers can’t be avoided presence disruption. One of the disturbances is short circuit immediately addressed. Therefore, to overcome the interference necessary in order not to cause damage protection system that meets the requirements of sensitivity, reliability, selectivity, and speed, all of which depend on the correct setting of protection equipment. Protective equipment which is used for power tansformator is differential relays and overcurrent relays instructed Circuit Breaker (CB) function to open the contacts, so that disturbed power transformers can be separated from the system. Analysis from result test of Over Current Relay get is tms 0,27 on 150 kv with 0,39 on 20 kv and from the analysis calculation then obtained tms 0,614 on 150 kv with 0,1799 on 20 kv. Based on an analysis, setting relay over current are installed was correct and reliable for external fault transformator. And from analysis has performed with rele differential found differential relay found sensitive to internal fault transformator.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Transformator tenaga, rele diferensial, rele arus lebih, koordinasi proteksi Power Transformator, differential relay, overcurrent relay, coordination of protection
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 03 Dec 2025 05:44
Last Modified: 03 Dec 2025 05:44
URI: https://repository.itpln.ac.id/id/eprint/4354

Actions (login required)

View Item
View Item