Afiatanur, Ade Fani and Susanto, djoko (2018) PENGARUH PEMASANGAN KAPASITOR PADA JARINGAN TEGANGAN MENENGAH 20 kV DI PT.PLN AREA SUKABUMI PENYULANG CIPANENGAH YANG OPTIMUM. Diploma thesis, ITPLN.
ADE FANI A. S.T.pdf
Restricted to Registered users only
Download (1MB)
Sesudah Pemasangan Kapasitor.pdf
Download (497kB)
Sebelum pemasangan kapasitor.pdf
Download (524kB)
F2Report ETAP Sesudah.pdf
Download (83kB)
F1Report ETAP Sebelum.pdf
Download (83kB)
E1 SLD ETAP.pdf
Download (83kB)
D1 SLD Cipanengah.pdf
Download (124kB)
C1 Lampiran Harga Kapasitor.pdf
Download (86kB)
C1 Lampiran Harga Kapasitor.pdf
Download (86kB)
B1 lembar bimbingan.pdf
Download (149kB)
Sesudah pemasangan kapasitor 450 kvar.pdf
Download (76kB)
Sesudah pemasangan kapasitor 300 kvar.pdf
Download (76kB)
Sesudah pemasangan kapasitor 150 kvar.pdf
Download (76kB)
Sesudah pemasangan kapasitor 600 kvar.pdf
Download (76kB)
Single line diagram.pdf
Download (57kB)
Abstract
Pada jaringan distribusi tegangan menengah khususnya saluran udara tegangan menengah melayani beban-beban yang terdapat pada gardu distribusi. Beban pada setiap gardu distribusi tidak sama besarnya baik dari segi daya aktif maupun daya reaktif. Dengan menempatkan kapasitor pada jaringan tegangan menengah diharapkan beban daya reaktif bisa berkurang dan rugi-rugi daya dalam jaringan juga berkurang. Kapasitor ditempatkan dalam jaringan tegangan menengah dan diberi fasilitas untuk mengeluarkan dan memasukkan sebagian atau keseluruhan pemutus beban (PMT ) dari operasi tergantung perubahan beban dalam satu hari. Dari hasil penelitian ini didapatkan penempatan kapasitor yang optimum pada jaringan tegangan menengah 20 kV di PT PLN Area Sukabumi Penyulang Cipanengah terletak pada gardu distribusi ST dan DLH dikarenakan gardu ini sudah terlihat penurunan tegangan sebesar 4 % dan juga pada gardu ini merupakan titik pertengah dari penyulang area sukabumi cipanengah. Dengan terpasangnya kapasitor ini juga memiliki pengaruh penurunan tegangan pada ujung jaringan dan rugi – rugi daya. Salah satunya pada gardu distribusi RAK, tegangan sebesar 2,86 % atau sebesar 0,572 KV dan rugi rugi daya sebesar 0,005 KW dan 0.007 KVAR. Kemudian setelah pemasangan Kapasitor penurunan tegangan pada ujung jaringan pada gardu distribusi RAK sebesar 1,29 % atau sebesar 0,258 kV dan rugi rugi daya sebesar 0.004 KW dan 0.006 KVAR. Sehingga pada gardu distribusi RAK saat sebelum terpasang dan setelah terpasang kapasitor memiliki kenaikan tegangan sebesar 1,57 % atau 0,314 kV dan penurunan rugi –rugi daya sebesar 0.001 Kw dan 0,001 Kvar.
In the medium voltage distribution network, especially the medium-voltage airway (SUTM) serves the loads contained in the distribution substation. The load on each distribution substation is not the same magnitude either in terms of active power or reactive power. By placing the capacitor in the medium voltage network it is expected that the reactive power load can be reduced and the loss of power in the network also decreases. The capacitor is placed in a medium voltage network and is provided with the facility to remove and insert part or all of the load breaker (PMT) from operation depending on the load changes in one day. From this research, the optimum capacitor placement in 20 kV medium tension network in PT PLN Area Sukabumi Penyulang Cipanengah is located in substation of ST and DLH distribution because of this substation has seen a decrease of voltage equal to 4% and also at this substation is the middle point of penyulang area sukabumi cipanengah. With the installation of this capacitor also has the effect of voltage drop at the end of the network and loss-loss power. One of them on the RAK distribution substation, the voltage of 2.86% or equal to 0.572 KV and loss of power loss of 0.005 KW and 0.007 KVAR. Then after installation the voltage reduction capacitor at the end of the network at the RAK distribution substation of 1.29% or equal to 0.258 kV and loss of power loss of 0.004 KW and 0.006 KVAR. So at the RAK distribution post before the installed and after installed the capacitor has a voltage increase of 1.57% or 0.314 kV and decrease in loss-power loss of 0.001 Kw and 0.001 Kvar.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Jaringan Distribusi, Kapasitor , Rugi rugi daya, Penurunan Tegangan Distribution Network, Capacitors, Power Loss, Drop Voltage |