ANALISIS PENGUJIAN TAHANAN ISOLASI UNTUK MENILAI KEANDALAN KUBIKEL 20KV PADA GARDU DISTRIBUSI MK155 DAN MK88 PLN UP3 CENGKARENG

HUSAEN, ILHAM MOHAMAD and Husada, Hendrianto (2025) ANALISIS PENGUJIAN TAHANAN ISOLASI UNTUK MENILAI KEANDALAN KUBIKEL 20KV PADA GARDU DISTRIBUSI MK155 DAN MK88 PLN UP3 CENGKARENG. Diploma thesis, ITPLN.

[thumbnail of TA_ILHAM MOHAMAD HUSAEN_202271014.pdf] Text
TA_ILHAM MOHAMAD HUSAEN_202271014.pdf
Restricted to Registered users only

Download (5MB)

Abstract

Keandalan sistem distribusi listrik sangat penting untuk menjaga kestabilan pasokan energi ke konsumen. Penelitian ini bertujuan untuk menganalisis keandalan sistem terhadap kubikel 20kV pada gardu distribusi MK155 dan MK88. Kubikel merupakan komponen penting yang berfungsi mengatur dan melindungi aliran listrik tegangan menengah agar tetap aman dan stabil. Diharapkan hasil penelitian ini dapat menjadi bahan pertimbangan untuk meningkatkan keandalan sistem distribusi listrik secara keseluruhan. Keandalan sistem distribusi listrik merupakan faktor krusial untuk menjamin pasokan energi yang stabil dan berkelanjutan bagi konsumen. Penelitian ini secara khusus berfokus pada analisis keandalan kubikel 20kV di dua gardu distribusi, yaitu Gardu MK155 dan Gardu MK88, yang berada di bawah pengelolaan PLN UP3 Cengkareng. Kubikel adalah komponen vital yang berfungsi mengendalikan, melindungi, dan mendistribusikan aliran listrik tegangan menengah agar tetap aman. Dalam studi ini, metode penelitian melibatkan pengumpulan dan analisis data hasil pengujian tahanan isolasi pada kubikel, yang bertujuan untuk mengidentifikasi potensi gangguan pada sistem. Hasil analisis menunjukkan bahwa meskipun nilai tahanan isolasi pada kedua gardu masih berada jauh di atas ambang batas standar minimum yang ditetapkan PLN, yaitu 20 MΩ, tren penurunan nilai perlu diperhatikan. Sebagian besar gangguan yang ditemukan di lapangan disebabkan oleh faktor eksternal, seperti cuaca ekstrem, gangguan hewan, dan kesalahan operasional. Rekomendasi yang d isarankan meliputi peningkatan sistem proteksi, pemeliharaan rutin, dan pengawasan berkala pada peralatan kubikel untuk meningkatkan keandalan sistem distribusi secara keseluruhan dan memastikan pasokan listrik yang optimal kepada pelanggan.

The reliability of a power distribution system is very important to maintain a stable supply of energy to consumers. This research aims to analyze the system's reliability of 20kV cubicles in the MK155 and MK88 distribution substations. Cubicles are important components that function to regulate and protect the flow of medium-voltage electricity to keep it safe and stable. It is hoped that the results of this research can be a consideration for improving the overall reliability of the electricity distribution system. The reliability of a power distribution system is a crucial factor in ensuring a stable and sustainable energy supply for consumers. This research specifically focuses on analyzing the reliability of 20kV cubicles in two distribution substations, namely MK155 and MK88, which are under the management of PLN UP3 Cengkareng. The cubicle is a vital component that functions to control, protect, and distribute medium-voltage electricity safely. In this study, the research method involves collecting and analyzing insulation resistance test data on the cubicles, with the aim of identifying potential system disturbances. The analysis results indicate that although the insulation resistance values in both substations are well above the minimum standard threshold set by PLN, which is 20 MΩ, a downward trend in these values should be noted. The majority of the disturbances found in the field are caused by external factors, such as extreme weather, animal interference, and operational errors. The recommended solutions include an improved protection system, routine maintenance, and periodic monitoring of the cubicle equipment to enhance the overall reliability of the distribution system and ensure an optimal power supply to customers.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: keandalan sistem, kubikel 20kV, gardu distribusi, gangguan listrik, pemeliharaan. system reliability, 20kV cubicles, distribution substations, electrical disturbances, maintenance.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Vokasi > D3 Teknologi Listrik
Depositing User: Sudarman
Date Deposited: 09 Dec 2025 01:10
Last Modified: 09 Dec 2025 01:10
URI: https://repository.itpln.ac.id/id/eprint/4487