MUSTAQIM, HUDZAIFAH NUR and Diantari, Retno Aita and Hariyati, Rinna (2020) ANALISIS PENGATURAN KECEPATAN MOTOR INDUKSI 3 KW 3 FASA 380 V MENGGUNAKAN VARIABLE FREQUENCY DRIVE PADA SISTEM COAL FEEDER DI PT. MERAK ENERGI INDONESIA. Diploma thesis, ITPLN.
30. PROYEK AKHIR_HUDZAIFAH NUR MUSTAQIM_201771145_HUDZAIFAH NUR MUSTAQ.pdf
Restricted to Registered users only
Download (2MB)
Abstract
Sistem Coal feeder merupakan salah satu sistem yang sangat penting di suatu
pembangkit listrik tenaga uap. Alat ini digunakan untuk menyuplai bahan bakar
batubara dari coal bunker ke boiler. Alat ini dilengkapi dengan variable vrequency
drive (VFD) yang bekerja sesuai dengan fungsinya, yaitu untuk mengatur
kecepatan motor penggerak belt coveyor sehingga batubara yang menyuplai
boiler dapat diatur jumlahnya, sehingga proses pembentukan panas di boiler
dapat berjalan dengan baik dan efisien. VFD memiliki setting 4mA-20mA
sehingga kecepatan putar motor dapat divariasikan sesuai dengan setting
tersebut, dan menyebabkan jumlah batubara yang mampu diangkut perjamnya
juga bervariasi tergantung kecepatan putar motor. Dari penelitian didapatkan
pada setting VFD 4mA kecepatan motor yang dihasilkan 0Rpm sehingga
batubara yang mampu diangkut sebesar 0Ton/jam. Sedangkan pada setting
20mA kecepatan motor yang dihasilkan adalah 1500Rpm sehingga batubara
yang mampu diangkut sebesar 18,27Ton/jam.
Coal feeder system is one of the most important systems in a steam power plant.
This tool is used to supply coal fuel from coal bunkers to boilers. This tool is
equipped with a variable vrequency drive (VFD) that works in accordance with its
function, namely to regulate the speed of the motor drive belt coveyor so that the
coal that supplies the boiler can be regulated in number, so that the process of
forming heat in the boiler can run well and efficiently. VFD has a setting of 4mA
20mA so that the motor rotational speed can be varied according to these settings, and cause the amount of coal that can be transported per hour also varies depending on the motor rotational speed. From the research, it is found that the 4FA VFD setting of the motor speed produced is 0Rpm so that coal that can be transported is 0 Ton / hour. Whereas at the setting of 20mA the speed of the motor produced is 1500Rpm so that coal that can be transported is 18.27Tons / hour.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Konverter Frekuensi, Pengumpan Batubara, Bahan Bakar Variable Frequency Drive (VFD), Coal Feeder, Fuel |
| Subjects: | Skripsi Bidang Keilmuan > Tenaga Listrik |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Nurul Hidayati |
| Date Deposited: | 10 Feb 2026 12:19 |
| Last Modified: | 10 Feb 2026 12:19 |
| URI: | https://repository.itpln.ac.id/id/eprint/4974 |