YULISTYANTO, AFIF WIDYAR and oktaviana, tri wahyu (2019) DIAGNOSA PENYULANG 20 KV TEROMPAH DENGAN PENGUKURAN PARTIAL DISCHARGE PADA SEGMEN GD71 - MN47 DAN GD71 – MN51 DI AREA PONDOK GEDE. Diploma thesis, ITPLN.
Tugas Akhir 4xRevisi.pdf
Restricted to Registered users only
Download (2MB)
Abstract
Sistem distribusi tegangan menengah di Jakarta saat ini hampir secara kesuluruhan menggunakan sistem saluran kabel tegangan menengah (SKTM). SKTM lebih dipilih karena lebih rapi dan efisiensi tata kotanya lebih teratur dibandingkan SUTM. Dari kedua sistem penyaluran tegangan menengah tersebut tidak akan luput daripada gangguan, terutama SKTM. Hal ini tentu merupakan sebuah tantangan bagi PT. PLN untuk mengurangi jumlah gangguan sehingga bisa meningkatkan kehandalan sistem distribusi. Untuk menghindari kegagalan pada sistem kabel perlu pengecekkan secara berkala dengan melakukan asesmen kabel dengan peralatan-peralatan yang lengkap. Asesmen kabel dengan menggunakan metode Very Low Frequency (VLF) yang mana dalam pengujiannya dapat mengukur partial discharge-nya dengan memberikan tegangan uji. Beberapa prosedur untuk melakukan asesmen kabel adalah Monitored Wishatstone Test dan pengukuran Partial Discharge: (1) Monitored Wisthand Test (MWT), pengujian isolasi kabel dan mengukur arus bocor yang dilakukan secara bertahap pada masing-masing fasanya; (2) Pengukuran Partial Discharges (PD), untuk mengukur besaran muatan yang keluar akibat kegagalan isolasi. Objek yang menjadi penelitian berada di Gardu GD71 sebagai tempat pengukuran PD untuk segmen GD71 – MN47 dan GD71 – MN51. Menghasilkan laporan hasil uji kedua segmen bahwa kabel mengalami kondisi kritis karena banyak PD Level Max dengan satuan piko Coulumb lebih besar dari 1000pC dan PDIV yang terdeteksi di bawah tegangan nominal (U0) dengan satuan kilo Volt. Ketika hasil pengukuran dibandingkan dengan hasil perhitungan serta dengan memakai persamaan rumus kapasitansi yang dihasilkan dari kedua plat sejajar, maka selisih nilai perbandingannya sangat tipis.
The medium voltage distribution system in Jakarta is currently almost entirely using a Medium Voltage Cable Lines system. Medium Voltage Cable Lines are preferred because they are neater and the layout efficiency is more organized then Medium Voltage Air Lines. The two medium voltage distribution systems will not escape interference, especially the Medium Voltage Cable Lines. This certainly is a challenge for PLN to reduce the number of disruptions so that it can improve the reliability of the distribution system. To avoid failures in the cable system, it is necessary to check periodically by conducting a cable assessment with complete equipment. Cable assessment using the Very Low Frequency (VLF) method which in its test can measure its Partial Discharge by providing a test voltage. Some procedures for conducting cable assessments are Monitered Withstand Test (MWT) and Partial Discharge measurements : (1) Monitored Withstand Test (MWT), testing the cable insulation and measuring the leakage current which is carried out in stages in each phase; (2) Partial Discharge (PD) measurement, to measure the amount of load. The object being researched was at the GD71 substation of a place for measuring PD for the segments GD71 – MN47 and GD71 – MN51. Generate a report on the results of the second segment test that connects the crtical cable with PD Level Max with one pico Coulumb greater than 1000pC and PDIV using a nominal value below the nominal voltage (U0) in kilo Volts. When the measurement results are compared with the calculation results and by using the equation of the capacitance formula produced from the two parallel plates, the difference in the value of the comparison is very thin.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Saluran kabel Tegangan Menengah (SKTM), Very Low Frequency (VLF), Monitored Wisthand Test (MWT), Partial Discharge Medium Voltage Cable Lines (SKTM), Very Low Frequency, Monitored Wisthand Test, Partial Discharge. |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 12 Feb 2026 08:58 |
| Last Modified: | 12 Feb 2026 08:58 |
| URI: | https://repository.itpln.ac.id/id/eprint/5017 |