SETTING KOORDINASI OCR & GFR DI INCOMING FEEDER, OUTGOING FEEDER DAN GARDU DISTRIBUSI E146 PENYULANG PANTRI GARDU INDUK CIPINANG

RIFQIANSYAH, MUHAMMAD and suwarno, suwarno (2019) SETTING KOORDINASI OCR & GFR DI INCOMING FEEDER, OUTGOING FEEDER DAN GARDU DISTRIBUSI E146 PENYULANG PANTRI GARDU INDUK CIPINANG. Diploma thesis, ITPLN.

[thumbnail of TUGAS AKHIR.pdf] Text
TUGAS AKHIR.pdf
Restricted to Registered users only

Download (3MB)

Abstract

Sistem distribusi tenaga listrik tidak akan lepas dari suatu gangguan hubung singkat pada jaringan baik yang diakibatkan oleh faktor internal maupun eksternal. Gangguan yang mungkin terjadi dapat menimbulkan kerusakan pada peralatan distribusi maupun beban-beban listrik apabila gangguan tersebut tidak segera diisolir oleh perangkat proteksi. Salah satu proteksi utama dalam jaringan tenaga listrik adalah relay arus lebih (over current relay) dan relai gangguan tanah (ground fault relay). Dalam penentuan setting relay arus lebih, antara satu titik relay dengan relay yang lain harus saling berhubungan sehingga semua relay proteksi terkoordinasi dengan baik. Sistem distribusi tenaga listrik di PT.PLN (PERSERO) UP3 Pondok Kopi pada penyulang pantri terjadi relokasi jaringan. Untuk itu dilakukan penyetelan ulang perencanaan koordinasi relay arus lebih pada sistem distribusi tenaga listrik di PT.PLN(PERSERO) UP3 Pondok Kopi. Penelitian dilakukan mulai dengan pengumpulan data kelistrikan yang diperlukan. Kemudian membuat perencanaan single line diagram. Kemudian menentukan titik letak relay arus lebih dan mengitung nilai arus hubung singkat di titik terdekat. Setelah semua data terkumpul dan digunakan untuk semua setting relay arus lebih, kemudian dilakukan perhitungan penyetelan relay dan penggambaran kurva koordinasi relay arus lebih. Hasil perhitungan nilai setting relai di gardu distribusi adalah untuk OCR nilai arus primernya adalah 300 A, TMS-nya 0,11 dan waktunya 0,3 detik. Untuk GFR nilai arus primernya 77,17 A, TMS-nya 0,1 dan waktunya 0,3 detik. Relai di Outgoing feeder dalah untuk OCR nilai arus primernya 300 A, TMS-nya 0,26 dan waktunya 0,7 detik. Untuk GFR nilai arus primernya 77,1 ,TMS-nya 0,23 dan waktunya 0,7 detik. Relai pada Incoming feeder adalah untuk OCR nilai arus primernya 1732 A, TMS-nya 0,33 dan waktunya 1,1. Untuk GFR nilai arus primernya 95,49 A, TMS-nya 0,37 dan waktunya 1,1 detik.

Electric power distribution system will not be separated from a short circuit interference on the network either caused by internal or external factors. Interference that might occur can cause damage to distribution equipment and electrical loads if the interference is not immediately isolated by the protection device. One of the main protections in electric power networks is overcurrent relays. In determining the overcurrent relay settings, between one relay point and another relay must be interconnected so that all protection relays are well coordinated. The electric power distribution system at PT PLN (PERSERO) UP3 Pondok Kopi at pantri feeders occurs with network relocation. For this reason, the re-planning of overcurrent relay coordination in the electric power distribution system at PT PLN (PERSERO) UP3 Pondok Kopi is done. The study was conducted starting with the collection of electrical data needed. Then make a single line diagram plan. Then determine the location of the overcurrent relay and calculate the value of the short circuit current at the closest point. After all data has been collected and used for all overcurrent relay settings, then the relay adjustment calculation is performed and the overcurrent relay coordination curve is described. The calculation results of the relay setting value in the distribution substation are for OCR the primary current value is 300 A, the TMS is 0.11 and the time is 0.3 seconds. For GFR the primary current value is 77.17 A, the TMS is 0.1 and the time is 0.3 seconds. The relay in the Outgoing feeder is for OCR the primary current value is 300 A, the TMS is 0.26 and the time is 0.7 seconds. For GFR the primary current value is 77.1, the TMS is 0.23 and the time is 0.7 seconds. The relay in the Incoming feeder is for OCR the primary current value is 1732 A, the TMS is 0.33 and the time is 1.1. For GFR the primary current value is 95.49 A, the TMS is 0.37 and the time is 1.1 seconds.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: OCR,GFR, protection, transformer OCR, GFR,Proteksi, trafo