PENAMBAHAN GFD PADA GARDU DISTRIBUSI UNTUK MENGURANGI NILAI ENS (KWH TIDAK TERJUAL) DI PT. PLN UP3 SERPONG

SITANGGANG, APRIYOAN PRASETYA and Pahiyanti, Novi Gusti (2019) PENAMBAHAN GFD PADA GARDU DISTRIBUSI UNTUK MENGURANGI NILAI ENS (KWH TIDAK TERJUAL) DI PT. PLN UP3 SERPONG. Diploma thesis, ITPLN.

[thumbnail of 1. COVER TUGAS AKHIR-dikonversi (1).pdf] Text
1. COVER TUGAS AKHIR-dikonversi (1).pdf

Download (46kB)
[thumbnail of 2. LEMBAR PENGESAHAN - DAFTAR ISI-dikonversi (2).pdf] Text
2. LEMBAR PENGESAHAN - DAFTAR ISI-dikonversi (2).pdf

Download (119kB)
[thumbnail of PROYEK AKHIR YOAN ASLI-dikonversi (2).pdf] Text
PROYEK AKHIR YOAN ASLI-dikonversi (2).pdf
Restricted to Registered users only

Download (750kB)

Abstract

Salah satu tugas utama perusahaan listrik adalah menghasilkan tenaga listrik yang dapat diandalkan oleh pelanggan. Gangguan pasokan listrik semakin tidak dapat ditolerir oleh pelanggan karena dampak sosial dan ekonomi yang sangat berat. Keandalan pasokan merupakan salah satu faktor kunci dalam pengambilan keputusan untuk pengembangan sistem pembangkit, transmisi dan distribusi tenaga listrik. Permasalahan yang sering terjadi pada saluran distribusi adalah gangguan hubung singkat dan gangguan lainnya, Seringkali lokasi gangguan tidak langsung terdeteksi / tidak dapat segera diketahui letak lokasinya, sehingga memperlambat proses penanganan gangguan Untuk memenuhi tuntutan tersebut PLN menggunakan teknologi distribusi yang bisa diandalkan kualitasnya, yaitu Ground Fault Detector (GFD). Pada tulisan ini dikemukakan cara pendeteksian gangguan dengan bantuan alat Ground Fault detector sehingga lebih cepat diketahui letak gangguannya. Hasilnya menunjukkan bahwa sebelum pemasangan GFD lama pengusutan gangguan pada tahun 2017 pergangguan yaitu 103 menit sedangkan tahun 2018 yang sudah dipasang GFD yaitu menjadi 48 menit dan PLN juga dapat mengurangi kWh yang tak terjual sehingga PLN dapat berhemat sebesar Rp 8.471.925 per gangguan setelah GFD terpasang.

One of the main tasks of an electric company is to produce electricity that can be relied on by customers. The disruption of electricity supply is increasingly intolerable to customers because of very heavy social and economic impacts. Supply reliability is one of the key factors in making decisions for the development of electric power generation, transmission and distribution systems. Problems that often occur in distribution channels are short circuit disturbances and other disturbances. Often the location of the disturbance is not immediately detected / cannot be immediately known where the location is, thus slowing down the handling process. To meet these demands PLN uses reliable quality distribution technology, namely Ground Fault Detector (GFD). In this paper, it is proposed how to detect interference with the help of a Ground Fault detector so that the location of the fault is faster. The results show that before the installation of the old GFD disturbance in 2017 the disturbance was 103 minutes while in 2018 the GFD had been installed which was 48 minutes and PLN could also reduce the unsold kWh so that PLN could save Rp 8,471,925 per disturbance after the GFD was installed .

Item Type: Thesis (Diploma)
Uncontrolled Keywords: GFD (Ground Fault Detector), interference current, Isolating Disorders. GFD (Ground Fault Detector), Arus gangguan, Mengisolir Gangguan.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Vokasi > D3 Teknologi Listrik
Depositing User: Sudarman
Date Deposited: 18 Feb 2026 04:10
Last Modified: 18 Feb 2026 07:47
URI: https://repository.itpln.ac.id/id/eprint/5077

Actions (login required)

View Item
View Item