PERBAIKAN TAHANAN PENTANAHAN DENGAN METODE PEMASANGAN GROUNDING SUNTIK PADA GI WATES

BANTARI, BAGASVARA WIRAYUDHA and makkulau, andi (2018) PERBAIKAN TAHANAN PENTANAHAN DENGAN METODE PEMASANGAN GROUNDING SUNTIK PADA GI WATES. Diploma thesis, ITPLN.

[thumbnail of 1. COVER.pdf] Text
1. COVER.pdf

Download (47kB)
[thumbnail of 2. Lembar Pengesahan.pdf] Text
2. Lembar Pengesahan.pdf

Download (250kB)
[thumbnail of 7. Abstrak.pdf] Text
7. Abstrak.pdf

Download (92kB)
[thumbnail of 9. Bab I.pdf] Text
9. Bab I.pdf

Download (288kB)
[thumbnail of 10. Bab II.pdf] Text
10. Bab II.pdf

Download (499kB)
[thumbnail of 11. Bab III.pdf] Text
11. Bab III.pdf
Restricted to Registered users only

Download (490kB)
[thumbnail of 12. Bab IV.pdf] Text
12. Bab IV.pdf
Restricted to Registered users only

Download (756kB)
[thumbnail of 13. Bab V.pdf] Text
13. Bab V.pdf
Restricted to Registered users only

Download (194kB)

Abstract

Sistem pentanahan pada GI Wates terletak di daerah pantai dan memiliki struktur tanah yang berlapis, dan juga kinerja arrester jaringan yang digunakan untuk memotong surja petir tak langsung tidak dapat bekerja secara optimal, yang menyebabkan tingginya angka PMT trip dan isolator flash. Hal tersebut diakibatkan oleh angka tahanan pentanahannya yang melebihi standar dari PLN yaitu <5 ohm. Oleh sebab itu tahanan pentanahan di daerah GI Wates harus diperbaiki dengan cara menanam grounding suntik pada rise pole GI Wates, sehingga nilai tahanan grounding menjadi <5 ohm. Dengan hasil nilai tahanan pentanahan yang dibawah 5 ohm, maka itu sesuai dengan standar PLN dan akan memberikan peranan yang sangat penting bagi keselamatan manusia yang ada di sekitar gardu induk. Analisa dari tugas akhir ini adalah untuk mendapatkan nilai tahanan pentanahan yang minimum pada sistem pentanahan grounding suntik.

The earthing system of Wates substation is located in the coastal area and has a layered soil structure, and also the performance of arrester used to cut indirect lightning surge not working optimally leading to high PMT trip and isolator flash. This is due to the number of ground resistances which exceeds the standard of PLN <5 ohms. Therefore, the grounding system in the Wates substation area must be repaired by planting the syringe grounding all over at the rise pole Wates substation, the base of the resistance value becomes <5 ohms. With the value of grounding resistance values below 5 ohms, then it is in accordance with the standards of PLN and will provide a very important role for human safety around the substation. The analysis of this final project is to find the minimum rating on the injection grounding system.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: syringe grounding, grounding system, lightning surge. grounding suntik, tahanan pentanahan, surja petir.