AULIYA, SITI and handayani, oktaria (2018) UPAYA MENGATASI JATUH TEGANGAN DAN RUGI DAYA PADA JARINGAN TEGANGAN RENDAH DENGAN PEMBANGUNAN GARDU SISIP TIPE PORTAL. Diploma thesis, ITPLN.
1. Cover.pdf
Download (33kB)
2. Lembar pengesahan.pdf
Download (65kB)
abstrak indonesia.pdf
Download (247kB)
abstrack Inggris.pdf
Download (79kB)
BAB I.pdf
Download (42kB)
BAB II.pdf
Download (429kB)
BAB III.pdf
Restricted to Registered users only
Download (216kB)
BAB IV.pdf
Restricted to Registered users only
Download (560kB)
BAB V.pdf
Restricted to Registered users only
Download (29kB)
DAFTAR PUSTAKA.pdf
Download (9kB)
Abstract
Dalam sistem keandalan penyaluran tenaga listrik yang diperhatikan adalah kualitas tegangan yang baik dan stabil, karena meskipun kelangsungan suplai energi listrik dapat diandalkan, namun tetap akan terjadi jatuh tegangan. Faktor lain yang ikut mempengaruhi perubahan tegangan sistem adalah rugi daya yang disebabkan oleh adanya impedansi seri penghantar saluran, rugi daya ini menyebabkan jatuh tegangan. Oleh karena itu konsumen yang letaknya jauh dari titik pelayanan akan cenderung menerima tegangan relatif lebih rendah, bila dibandingkan dengan tegangan yang diterima konsumen yang letaknya dekat dengan pusat pelayanan. Adanya jatuh tegangan pada tiang ujung penerima dapat menyebabkan arus jaringan menjadi tinggi sehingga losses yang terjadi pada jaringan tersebut meningkat. Untuk mengatasi masalah tersebut maka dilakukan perbaikan jaringan dengan cara membangun gardu distribusi sisipan sehingga dapat memperbaiki mutu tegangan dan meminimalisir rugi daya pada jaringan. Dari hasil perhitungan persentase nilai jatuh tegangan di PT.PLN Area Cikupa sebelum pemasangan gardu sisip sebesar 10,6% untuk phasa S jurusan 1 dan 11,7% untuk phasa S jurusan 4 dimana nilai tersebut tidak sesuai dengan SPLN N0.1 tahun 1995, batas toleransi variasi tegangan pelayanan sebagai akibat rugi tegangan adalah maksimal +5% dan minimal -10% pada sisi pelayanan. Setelah dilakukan pemasangan gardu sisip, nilai jatuh tegangan menjadi 5,1% untuk phasa S jurusan 1 dan 6,1% untuk phasa S jurusan 4 dimana nilai tersebut sudah sesuai dengan standar.
In the system of reliability of electric power distribution that is concerned is good and stable voltage quality, because although the continuity of the supply of electrical energy is reliable, but still there will be a voltage drop. Another factor that affects the system voltage change is the power loss caused by the impedance of the conductor channel series, this power loss causes a voltage drop. Consumers who are located far from the service point tend to receive relatively lower stresses, when compared to the voltage received by consumers who are located close to the service center. The existence of a voltage drop on the receiving end pole can cause the network current to be high so that losses that occur in the network increases. To overcome these problems then performed network repair by building substation distribution insertion so as to improve the quality of the voltage and minimize the loss of power on the network. From the calculation of the percentage value of the voltage drop in PT. PLN Area Cikupa before the installation of the substation is 10.6% for the S phase 1 and 11.7% for the S phase 4, the value is not in accordance with SPLN No. 1 of 1995, the tolerance limit of service voltage variation as a result of voltage loss is a maximum of + 5% and a minimum of -10% at the service side. After the installation of the substation was installed, the voltage dropped to 5.1% for the S phase 1 and 6.1% for the S phase 4, where the value was in accordance with the standard.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Insertion, voltage drop, power loss, efforts to overcome voltage drop and electric power loss. Gardu sisip, jatuh tegangan, rugi daya, upaya mengatasi jatuh tegangan dan rugi daya listrik. |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 19 Feb 2026 07:28 |
| Last Modified: | 19 Feb 2026 07:28 |
| URI: | https://repository.itpln.ac.id/id/eprint/5134 |