PENGARUH KEJENUHAN TRAFO ARUS PADA PENYULANG ALENGKA DI GAS INSULATED SWICTHGEAR GAMBIR LAMA

ALKODRI, FAHMI and Widyastuti, Christine (2018) PENGARUH KEJENUHAN TRAFO ARUS PADA PENYULANG ALENGKA DI GAS INSULATED SWICTHGEAR GAMBIR LAMA. Diploma thesis, ITPLN.

[thumbnail of 0. COVER.pdf] Text
0. COVER.pdf

Download (198kB)
[thumbnail of Lembar pengesahan pembimbing.pdf] Text
Lembar pengesahan pembimbing.pdf

Download (317kB)
[thumbnail of abstrak indonesia.pdf] Text
abstrak indonesia.pdf

Download (268kB)
[thumbnail of abstrak english.pdf] Text
abstrak english.pdf

Download (268kB)
[thumbnail of BAB I Latar Belakang.pdf] Text
BAB I Latar Belakang.pdf

Download (187kB)
[thumbnail of BAB II Landasan Teori.pdf] Text
BAB II Landasan Teori.pdf

Download (540kB)
[thumbnail of BAB III.pdf] Text
BAB III.pdf
Restricted to Registered users only

Download (455kB)
[thumbnail of BAB IV .pdf] Text
BAB IV .pdf
Restricted to Registered users only

Download (532kB)
[thumbnail of BAB V .pdf] Text
BAB V .pdf
Restricted to Registered users only

Download (6kB)
[thumbnail of DAFTAR PUSTAKA.pdf] Text
DAFTAR PUSTAKA.pdf

Download (5kB)

Abstract

Sistem distribusi tenaga listrik merupakan sistem distribusi yang berguna untuk menyalurkan tenaga listrik dari sumber daya listrik besar sampai ke konsumen, pada sistem distribusi harus terdapat sistem proteksi sebagai pengaman sistem dari kemungkinan gangguan yang dapat terjadi. Dalam sistem proteksi, output trafo arus (CT) digunakan sebagai input untuk alat proteksi yang nantinya akan mentriger alat proteksi untuk bekerja bila ada gangguan. Untuk itu kejenuhan CT harus diperhatikan agar sistem proteksi dapat bekerja dengan benar. Pengaruh kejenuhan trafo arus pada pembahasan ini merupakan trafo arus untuk pengaman Tegangan Menengah 20kV.Dari hasil perhitungan arus gangguan hubung singkat maksimum pada penyulang alengka menghasilkan arus I3 fasa max sebesar 13,895 kA, Untuk trafo arus pada penyulang alengka dengan rasio 400/5 dengan batas kejenuhan sebesar 4,88 kA sehingga trafo arus akan terjadi kejenuhan jika terdapat arus gangguan hubung singkat maksimum. Apabila terjadi kejenuhan pada trafo arus maka relai arus lebih tidak bisa bekerja dikarenakan nilai rms pada trafo arus sisi sekunder error dan menyebabkan bekerjanya proteksi pada sisi hulunya akan bekerja dan mengakibatkan pemadaman semakin meluas.

Electricity distribution system is a distribution system that used to distribute electric power from large power sources to the consumer. The distribution system must have a protection system as a system safeguard from possible interference that can occurs. In the protection system, the current transformer output (CT) is used as an input for the protective device which will protect the protection device to work when there is interference on system.Therefore the saturation of Current Transformer must be considered in order to make the protection system work properly. The effect of current transformer saturation in this discussion is a current transformer for the 20kV Medium Voltage customers. From the calculation result of the maximum short circuit current,the alengka feeders produces the max phase I3 current of 13.895 kA, as for the current transformer on the alengka feeders with the ratio of 400/5 on CT and the saturation limit of 4.88 kA. From that result, we can predict that saturation will occur in current transformer if there is a maximum short circuit current on systems. If there is saturation in the current transformer, the overcurrent relays will not work properly. Caused by error on the rms value on the secondary side of current transformer that will make protection system on the upstream side to work and resulting in wider blackouts spread.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Protection System, Over Current Relay, Current Transformer (CT) Sistem Proteksi, Relai Arus Lebih, Trafo Arus (CT)
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Vokasi > D3 Teknologi Listrik