PENURUNAN KAPASITAS DAYA TRAFO AKIBAT PENGARUH HARMONISA PADA TRAFO DISTRIBUSI TIPE PORTAL 250 KVA DI PT. PLN (Persero) UPJ TANDES

Wijaya, Eka Pungki and Ispranyoto, Edy (2018) PENURUNAN KAPASITAS DAYA TRAFO AKIBAT PENGARUH HARMONISA PADA TRAFO DISTRIBUSI TIPE PORTAL 250 KVA DI PT. PLN (Persero) UPJ TANDES. Diploma thesis, ITPLN.

[thumbnail of 1. Hal Judul Proposal Skripsi.pdf] Text
1. Hal Judul Proposal Skripsi.pdf

Download (63kB)
[thumbnail of 2. Lembar pengesahan pembimbing.pdf] Text
2. Lembar pengesahan pembimbing.pdf

Download (29kB)
[thumbnail of 7. Abstrak Bhs Indo.pdf] Text
7. Abstrak Bhs Indo.pdf

Download (11kB)
[thumbnail of 8. Abstrak Bhs Inggris.pdf] Text
8. Abstrak Bhs Inggris.pdf

Download (10kB)
[thumbnail of 12.BAB I Pendahuluan.pdf] Text
12.BAB I Pendahuluan.pdf

Download (42kB)
[thumbnail of 13.BAB II Landasan Teori.pdf] Text
13.BAB II Landasan Teori.pdf

Download (574kB)
[thumbnail of 14. Bab III metode penelitian.pdf] Text
14. Bab III metode penelitian.pdf
Restricted to Registered users only

Download (242kB)
[thumbnail of 15. Bab IV hasil dan pembahasan.pdf] Text
15. Bab IV hasil dan pembahasan.pdf
Restricted to Registered users only

Download (595kB)
[thumbnail of 16. Bab V penutup.pdf] Text
16. Bab V penutup.pdf
Restricted to Registered users only

Download (15kB)
[thumbnail of 17. Daftar pustaka.pdf] Text
17. Daftar pustaka.pdf

Download (30kB)

Abstract

Tingkat harmonisa yang tinggi sangat berpengaruh pada kinerja transformator, pengaruh tersebut adalah rugi-rugi pada transformator yang semakin meningkat. Oleh sebab itu, akibat dari peningkatan rugi-rugi tersebut penurunan kapasitas daya transformator akan terjadi. Sehingga dalam proyek akhir ini dilakukan pengambilan data dengan menggunakan sampling gardu distribusi tipe portal di AC.263 dengan kapasitas daya 250 kVA, dengan mengacu pada standar SPLN D5.004-21.2012. Dari hasil perhitungan diperoleh nilai Total Harmonic Distortion (THD) untuk arus pada fasa R sebesar 16,401 %, fasa S sebesar 19,019 % dan fasa T sebesar 15,202 % sedangkan untuk Total Harmonic Distortion (THD) untuk tegangan pada fasa R sebesar 2,586 %, fasa S sebesar 2,048 % dan fasa T sebesar 2,030 % dari hasil tersebut THD untuk arus pada masing-masing fasa sudah melebihi batas standar yang ditentukan dan untuk THD pada tegangan pada masing-masing fasa masih dibawah standar yang ditentukan. Oleh karena itu diperlukan analisis koreksi rugi-rugi transformator akibat dari nilai THD arus yang melebihi batas standar,acuan yang digunakan dalam melakukan analisis koreksi perhitungan rugi-rugi adalah standar IEEE C57.110-1998.Dari analisa perhitungan yang telah dilakukan diperoleh hasil bahwa harmonisa meningkatkan rugi-rugi berbeban pada rugi tembaga sebesar 65,672 W, rugi belitan arus eddy sebesar 692,279 W dan rugi sasar lain sebesar 954,179 W sehingga terjadi penurunan kapasitas daya trafo akibat harmonisa sebesar 1,821 kVA.

High level of harmonics greatly affect the performance of transformers, the effect is the losses on the transformer is increasing. Therefore, as a result of the increase in losses the decrease in transformer power capacity will occur. So in this final project is done data retrieval by using portal type distribution substation in AC.263 with power capacity 250 kVA, with reference to SPLN standard D5.004-21.2012. The calculation result obtained by Total Harmonic Distortion (THD) value for current at R phase equal to 16,401%, S phase equal to 19,019% and phase T equal to 15,202% while for Total Harmonic Distortion (THD) for the voltage at the R phase of 2.586%, the S phase of 2.048% and the T phase of 2.030% of the result THD for the current on each phase has exceeded the specified standard limitand for THD the voltage at each phase is still below the specified standard. Therefore, a correction analysis of the transformer losses resulted from the current THD value exceeding the standard limit, the reference used in performing the correction analysis of loss calculations is IEEE C57.110-1998 standard. From the calculation analysis that has been done, the result that harmonics increase the burden of losses at loss of copper equal to 65,672 W, winding eddy current loss of 692,279 W and other stray loss of 954,179 W so that there is a decrease in transformer power capacity due to harmonics of 1.821 kVA.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Harmonics, Transformer, Losses, Winding Eddy Current Loss, Other Stray Loss, Copper Loss. Harmonisa,Transformator ,Rugi-Rugi, Rugi Belitan Arus Eddy, Rugi Sasar Lain, Rugi Tembaga.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Vokasi > D3 Teknologi Listrik
Depositing User: Sudarman
Date Deposited: 20 Feb 2026 01:40
Last Modified: 20 Feb 2026 01:40
URI: https://repository.itpln.ac.id/id/eprint/5157