PENGARUH PERUBAHAN REAKTANS DAN RESISTANS UJI HUBUNG SINGKAT TERHADAP RUGI BELITAN PADA TRANSFORMATOR DISTRIBUSI

IBRAHIM, MIFTAH FAUZAN AKMAL and Hidayat, Syarif (2018) PENGARUH PERUBAHAN REAKTANS DAN RESISTANS UJI HUBUNG SINGKAT TERHADAP RUGI BELITAN PADA TRANSFORMATOR DISTRIBUSI. Diploma thesis, ITPLN.

[thumbnail of 0. Cover.pdf] Text
0. Cover.pdf

Download (74kB)
[thumbnail of 1. Lembar Awal pengesahan.pdf] Text
1. Lembar Awal pengesahan.pdf

Download (139kB)
[thumbnail of 6. Abstrak dan Daftar Isi.pdf] Text
6. Abstrak dan Daftar Isi.pdf

Download (176kB)
[thumbnail of 7. BAB 1.pdf] Text
7. BAB 1.pdf

Download (211kB)
[thumbnail of 8. BAB 2.pdf] Text
8. BAB 2.pdf

Download (743kB)
[thumbnail of 9. BAB 3.pdf] Text
9. BAB 3.pdf
Restricted to Registered users only

Download (301kB)
[thumbnail of 10. BAB 4.pdf] Text
10. BAB 4.pdf
Restricted to Registered users only

Download (444kB)
[thumbnail of 11. BAB 5.pdf] Text
11. BAB 5.pdf
Restricted to Registered users only

Download (87kB)
[thumbnail of 12. Daftar Pustaka.pdf] Text
12. Daftar Pustaka.pdf

Download (65kB)

Abstract

Pengujian ketahanan hubung singkat merupakan mata uji jenis (type Test) pada SPLN D3 002-1:2007, sedangkan IEC 60076-1 mengkualifikasikan sebagai mata uji special test. Berdasarkan IEC 60076-5, ketahanan hubung singkat dibedakan menjadi ketahanan terhadap gaya dinamik dan termal. Untuk ketahanan dinamik dapat dilihat dengan cara mengukur perubahan reaktans sebelum dan sesudah pengujian hubung singkat, hal ini mengacu pada IEC 60076-5. Pada ketahanan termal pada penelitian ini dilihat dari perubahan resistans sebelum dan sesudah pengujian hubung singkat. Penelitian ini bertujuan mencari korelasi antara perubahan reaktans dan resistans hubung singkat terhadap rugi belitan pada transformator distribusi. Metode yang dipakai adalah metode kuantitatif, karena memiliki perhitungan untuk memproses data berupa angka-angka. Dari hasil penelitian reaktansi tidak menunjukan pengaruh pada rugi belitan karna persentase perubahannya tidak menunjukan adanya korelasi. Namun pada resistans dapat terlihat korelasinya pada trafo yang memiliki kapasitas 50 KVA, resistansi belitan sekundernya mengalami kenaikan sebesar 3,49%, lalu terlihat pada perubahan presentase rugi belitannya ikut naik pada tap 1 sebesar 2,22%, pada tap 3 sebesar 2,162 %, dan pada tap 7 sebesar 2,038 %.

The short circuit test is the one of type test in SPLN D3 002-1:2007, while IEC 60076-1 qualifying as special test. Based on IEC 60076-5 short circuit endurance is divided to dynamic force and thermal. Dynamic force can be seen with measurement of reactans before and after short circuit test, this based on IEC 60076-5. Thermal in this research can be seen with measurement of resistance before and after short circuit test. This research aims to find correlation between changes of percentage reactance and resistance to winding loss in ditribution transformer. The methode used is a quantitative method, because it has a calculation to process data and produce data in the form of numbers. From the result of this research, reactance not showing any effect on winding loss because change of percentage reactance not show the correlation. But on the resistance can be seen the correlation to the transformer with a capacity of 50 kVA, the resistance of the secondary winding has increased by 3,49%, Then seen the change in percentage loss turns go up, on tap 1 for 2,22%, on tap 3 for 2,162%, and on tap 7 for 2,038%.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: reactance and resistance short circuit, winding loss, distribution transformer reaktans dan resistans hubung singkat, rugi belitan, transformator distribusi
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Vokasi > D3 Teknologi Listrik
Depositing User: Sudarman
Date Deposited: 20 Feb 2026 02:18
Last Modified: 20 Feb 2026 02:18
URI: https://repository.itpln.ac.id/id/eprint/5159

Actions (login required)

View Item
View Item