Abstract
Sistem distribusi sebagai sistem penyaluran tenaga yang langsung berhubungan dengan pelanggan. Berhubungan dengan durasi pemutusan beban dan frekwensi pemutusan beban. Memiliki dua parameter untuk mengetahui keandalan sistem tenaga listrik yaitu System Average Interruption Frequency Index (SAIFI) dan System Average Interruption Duration Index (SAIDI). Beberapa tindakan yang dapat dilakukan untuk mengatasi gangguan yang terjadi pada jaringan spindel. Gangguan – gangguan yang terjadi berdampak penyaluran listrik langsung ke pelanggan. Saat terjadi gangguan, penyaluran listrik ke pelanggan terputus. Pada pembahasan kali ini mengenai perbandingan penyulang martil yang memiliki fasiltas SCADA dan penyulang masinis yang tidak memilki fasilitas SCADA. Dari hasil perhitungan penyulang martil diperoleh SAIDI 0,33 menit/pelanggan/tahun dan SAIFI sebesar 0,003 kali/perlanggan/tahun sedangkan penyulang masinis diperoleh SAIDI 1,60 menit/pelanggan/tahun dan SAIFI 0,019 kali/pelanggan/tahun. Dilihat dari hasil perhitungan penyulang martil lebih andal dari penyulang masinis. Dikarenakan penyulang martil memiliki fasilitas SCADA/Remote Control di middle point saat mencari titik gangguan memiliki recovery time lebih cepat dibandingkan penyulang masinis tidak memilki fasilitas SCADA/Remote Control.
Distribution system are directly related to the customer. Related to the duration of the load and frequency of the load disconnection. Having two parameters to know the reliability of the power System Average Interruption Frequency Index (SAIFI) and System Average Interruption Duration Index (SAIDI). Some things you can do to cope with the disruption that occurs on the network spindel. Disorders that occurs affects the distribution of electricity directly to customers. In the event of interruption, channeling electricity to customers disconnected. At this time the discussion about martil feeders comparison that has the facility of SCADA and masinis feeder who do not have facilities the SCADA. From the results of the calculation of the martil feeders retrieved SAIDI 0.33 seconds/customers/year and SAIFI of 0.003 times/perlanggan/year while masinis feeder gained SAIDI 1.60 seconds/customers/year and SAIFI 0.019 times/customer/year. Judging from the results of the calculations are more reliable martil feeders than the masinis feeders. Because the martil feeder has SCADA/Remote Control at middle point when searching for a point of disruption have recovery time faster than masinis feeder does not have facilities the SCADA/Remote Control.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Network Spindel, SAIDI, SAIFI, SCADA. Jaringan Spindel, SAIDI, SAIFI, SCADA. |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 23 Feb 2026 08:19 |
| Last Modified: | 23 Feb 2026 08:19 |
| URI: | https://repository.itpln.ac.id/id/eprint/5187 |