SUGIARTO, TEGUH and Buchari, Irvan (2017) IDENTIFIKASI KEGAGALAN STANDAR PRODUKSI MODUL GENERATOR HYPOCHLORITE PADA PLTU PT. PJB UP PAITON UNIT 1 & 2. Diploma thesis, ITPLN.
COVER.pdf
Download (63kB)
1. Lembar pengesahan.pdf
Download (67kB)
6. abstrak indonesia.pdf
Download (236kB)
7. abstrak bhs inggris.pdf
Download (68kB)
12. Bab 1.pdf
Download (50kB)
13. Bab 2 .pdf
Download (607kB)
14. Bab 3.pdf
Restricted to Registered users only
Download (408kB)
15. Bab 4.pdf
Restricted to Registered users only
Download (822kB)
16. Bab 5.pdf
Restricted to Registered users only
Download (37kB)
17. Daftar Pustaka.pdf
Download (9kB)
Abstract
Generator Hypochlorite merupakan peralatan utama yang terdapat pada Chlorination Plant yang memiliki fungsi untuk menghasilkan larutan sodium hypochlorite dengan proses elektrolisis air laut. Larutan sodium hypochlorite merupakan suatu cairan atau zat kimia yang digunakan untuk sistem air pendingin pada PLTU Paiton Unit 1 & 2. Penginjeksian larutan sodium hypochlorite bertujuan untuk melemahkan atau mencegah biota-biota laut agar tidak berkembang biak di dalam sistem pendingin atau instalasi-intalasi yang dilaluinya sehingga menyebabkan menurunnya efisiensi kerja pendingin dan dapat membahayakan pembangkit. Supaya generator hypochlorite beroperasi sesuai dosing dan kinerjanya tetap terjaga, maka dilakukan perawatan dengan melakukan pengecekan yang rutin seperti pengukuran tegangan pada cell modul dengan tujuan mengetahui permasalahan yang terjadi pada generator hypochlorite tersebut. Permasalahan yang biasa terjadi seperti unbalance volt, dan terjadinya penyumbatan. Tegangan nominal pada penelitian ini seharusnya 8,75 Volt dengan toleransi ± 2,4 Volt. Setelah diketahui dari hasil identifikasi bahwa terdapat masalah tidak normalnya tegangan dan terdapat endapan, maka dengan melakukan pembersihan pada cell modul yang bermasalah adalah tindakan yang tepat untuk membuat tegangan yang bermasalah kembali normal dan mencapai nilai nominal sehingga kinerja dari modul generator kembali optimal.
Hypochlorite Generator is the main equipment contained in Chlorination Plant which has function to produce sodium hypochlorite by sea water electrolysis process. Sodium hypochlorite is a liquid or chemical used for cooling water system at PLTU Paiton Unit 1 & 2. Injection of sodium hypochlorite aims to weaken or prevent marine biota so as not to breed in the cooling system or induced in the installation so can be Causing a decrease in coolant working efficiency and may harm the plant. In order the hypochlorite generator operate according to the dosing and its performance is maintained, it is maintained by routine checks such as measuring the voltage on the cell module in order to know the problems that occur in the hypochlorite generator. Common problems such as unbalance volts, and occurrence of blockages. The nominal voltage in this study should be 8.75 volts with a tolerance of approximately 2.4. After it is known from the result of identification that there is an unstable problem of stress and there is precipitate, then by cleaning the problematic cell module is the right action to make the problem voltage back to normal and reach the nominal value again so that the performance of the generator module returns optimally
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Hypochlorite Generator, Cell Module, Unbalance Volt, Dosing, Sodium Hypochlorit, Elektrolysis Generator Hypochlorite, Cell Modul, Unbalance Volt, Dosing, Sodium Hypochlorit, Elektrolisis |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 24 Feb 2026 06:48 |
| Last Modified: | 24 Feb 2026 06:48 |
| URI: | https://repository.itpln.ac.id/id/eprint/5238 |