UNDARIS, RIZKY and Hendri, Hendri (2024) ANALISIS PENGARUH PERUBAHAN TEKANAN VAKUM KONDENSOR TERHADAP EFEKTIVITAS KONDENSOR SEBELUM DAN SESUDAH OVERHAUL PADA BLOK 1 DI PLTGU UP MUARA TAWAR. Diploma thesis, ITPLN.
![[thumbnail of Tugas Akhir_Rizky Undaris_202012025.pdf]](https://repository.itpln.ac.id/style/images/fileicons/text.png)
Tugas Akhir_Rizky Undaris_202012025.pdf
Restricted to Repository staff only
Download (6MB)
Abstract
Adanya pertumbuhan industri yang saat ini semakin berkembang, dimana PLTGU menjadi salah satu jenis pembangkit listrik yang saat ini banyak digunakan di Indonesia. PT. Nusantara Power Unit Pembangkit Muara Tawar adalah salah satu pembangkit yang berperan dalam menyuplai listrik di Jawa dan Bali. Kinerja PLTGU dipengaruhi oleh komponen utama, termasuk kondensor, yang memiliki peran vital dalam pembangkitan sehingga kondensor perlu dijaga keoptimalannya. Tujuan dari penelitian ini adalah untuk mengetahui perubahan tekanan yang terjadi pada kondensor setelah dilakukannya overhaul yang nantinya berpengaruh terhadap efektivitas kondensor. Dimana dalam penelitian ini meliputi perhitungan LMTD, laju perpindahan panas, dan efektivitas kondensor. Diperoleh hasil setelah dilakukannya overhaul berdampak positif dimana kenaikan nilai efektivitas dari 40,3% menjadi 50% pada beban 50 MW dengan tekanan 0,047 Bar menjadi 0,048 Bar. Efektivitas kondensor mengalami kenaikan sebesar 9,7%. Dimana, ketika nilai vakum semakin tinggi maka mampu mempengaruhi efektivitas kondensor, semakin tinggi nilai vakum akan mempengaruhi nilai laju perpindahan panas yang akan semakin baik dan nilai LMTD mengalami kenaikan sebesar 0.76 ˚C sehingga nilai efektivitas kondensor meningkat. Kinerja kondensor dipengaruhi oleh tekanan vakum, kebersihan tube, pemeliharaan, kualitas dan suhu air pendingin, dan pengoperasian komponen pendukung kondensor.
There is industrial growth which is currently increasingly developing, where PLTGU is one type of power plant that is currently widely used in Indonesia. PT. Nusantara Power Unit Pembangkit Muara Tawar is one of the generators that plays a role in supplying electricity in Java and Bali. PLTGU performance is influenced by the main components, including the condenser, which has a vital role in the generation so the condenser needs to be maintained optimally. The aim of this research is to determine the pressure changes that occur in the condenser after an overhaul which will affect the effectiveness of the condenser. This research includes calculating LMTD, heat transfer rate and condenser effectiveness. The results obtained after the overhaul had a positive impact where the effectiveness value increased from 40,3% to 50% at a load of 50 MW with a pressure of 0.047 Bar to 0.048 Bar. Condenser effectiveness increased by 9,7%. Where, when the vacuum value is higher it can influence the effectiveness of the condenser, the higher the vacuum value will influence the heat transfer rate value which will be better and the LMTD value will increase by 0.76 ˚C so that the condenser effectiveness value will increase. Condenser performance is influenced by vacuum pressure, tube cleanliness, maintenance, quality and temperature of cooling water, and operation of condenser supporting components.
Item Type: | Thesis (Diploma) |
---|---|
Uncontrolled Keywords: | PLTGU, Kondensor, Tekanan Vakum, Efektivitas PLTGU, Condenser, Vacuum pressure, Effectiveness |
Subjects: | Skripsi Bidang Keilmuan > Teknik Mesin |
Divisions: | Fakultas Teknologi dan Bisnis Energi > S1 Teknik Mesin |
Depositing User: | Nurul Hidayati |
Date Deposited: | 09 Sep 2025 07:05 |
Last Modified: | 09 Sep 2025 07:05 |
URI: | https://repository.itpln.ac.id/id/eprint/725 |