ANALISIS KONTAMINAN PADA MINYAK TRANSFORMATOR 4 DI ULTG BEKASI DENGAN METODE REKLAMASI UNTUK MENINGKATKAN KEANDALAN MINYAK ISOLASI TRANSFORMATOR

Perdana, Farhan Naufal and Diantari, Retno Aita (2025) ANALISIS KONTAMINAN PADA MINYAK TRANSFORMATOR 4 DI ULTG BEKASI DENGAN METODE REKLAMASI UNTUK MENINGKATKAN KEANDALAN MINYAK ISOLASI TRANSFORMATOR. Diploma thesis, Institut Teknologi PLN.

[thumbnail of SKRIPSI 202211614 FARHAN NAUFAL PERDANA.pdf] Text
SKRIPSI 202211614 FARHAN NAUFAL PERDANA.pdf
Restricted to Repository staff only

Download (16MB)

Abstract

Transformator 4 GI Cikarang yang berada di ULTG Bekasi mengalami anomali yaitu kegagalan termal selulosa dan arching. Untuk mengetahui penyebab anomali dilakukan pengujian DGA (Dissolved Gas Analysis) dan BDV (Breakdown Voltage). Pada pengujian DGA dihasilkan nilai gas CO dan CO2 pada kondisi 3 sesuai standar IEEE C57.104-2008 dan gas C2H2 pada kondisi 4 sesuai standar IEEE C57.104-2008. Pada pengujian BDV dihasilkan nilai rata – rata yaitu 46,805 kV yaitu dibawah standar 50 kV sesuai standar SK DIR. No. 0520-2.K/DIR/2014. Untuk memperbaiki minyak isolasi dilakukan reklamasi dengan cara melakukan filter minyak isolasi dan menambahkan zat berupa Fuller's' earth powder untuk menyerap gas terlarut pada minyak trafo pada alat filter merek Kato Electric. Setelah dilakukan reklamasi, gas CO mengalami penurunan sebesar 530,5 ppm (64,38%) dari 824 ppm menjadi 293,5 ppm, gas CO2 mengalami penurunan sebesar 3821,75 (49%) dari 7775 ppm menjadi 3953,25 ppm, dan gas C2H2 mengalami penurunan sebesar 60,25 ppm (79,27%) dari 76 ppm menjadi 15,75 ppm. Nilai BDV menunjukkan kenaikan sebesar 38,8% dari 46,805 kV menjadi 64,97 kV diatas nilai standar 50 kV sesuai SK DIR. No. 0520-2.K/DIR/2014. Nilai TDCG dan BDV menjadi indikator keandalan minyak trafo, semakin kecil nilai TDCG dan nilai BDV semakin besar, maka semakin baik kinerja trafo.

Transformer 4 GI Cikarang in ULTG Bekasi experienced anomalies, namely cellulose thermal failure and arching. To find out the cause of anomaly, DGA (Dissolved Gas Analysis) and BDV (Breakdown Voltage) tests were carried out. DGA testing resulted in CO and CO2 values in condition 3 according to IEEE C57.104-2008 and C2H2 in condition 4 according to IEEE C57.104-2008. In BDV testing, the average value is 46.805 kV, which is below the 50 kV standard according to SK DIR. No. 0520-2.K/DIR/2014. To improve insulating oil, reclamation is carried out by filtering insulating oil and adding a chemical substance is Fuller's' earth powder to absorb dissolved gas in transformer oil in Kato Electric. After reclamation, CO gas decreased by 530 ppm (64,38%) from 824 ppm to 293.5 ppm, CO2 gas decreased by 3821,75 (49%) ppm from 7775 ppm to 3953.25 ppm, and C2H2 gas decreased by 60.25 ppm (79,27%) from 76 ppm to 15,75 ppm. BDV value increase of 18.165 kV (38,8%) from 46,805 kV to 64,97 kV above the standard value according to SK DIR. No. 0520-2.K/DIR/2014. TDCG and BDV values are indicators of transformer oil reliability, the smaller TDCG value and the greater BDV value, the better the transformer performance.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Minyak Isolasi Trafo, Reklamasi, DGA (Dissolved Gas Analysis), BDV (Breakdown Voltage). Transformer Insulation Oil, Reclamation, DGA (Dissolved Gas Analysis), BDV (Breakdown Voltage).
Subjects: Bidang Keilmuan > Electrical Engineering
Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Budi Herdiansyah
Date Deposited: 11 Sep 2025 04:18
Last Modified: 11 Sep 2025 04:18
URI: https://repository.itpln.ac.id/id/eprint/903