ANALISIS KINERJA LIGHTNING ARRESTER SEBAGAI PENGAMAN TRANSFORMATOR DAYA DI GARDU INDUK 150kV KEMAYORAN TERHADAP GANGGUAN SURJA PETIR

Febriansyah, Yudha and suwarno, suwarno (2018) ANALISIS KINERJA LIGHTNING ARRESTER SEBAGAI PENGAMAN TRANSFORMATOR DAYA DI GARDU INDUK 150kV KEMAYORAN TERHADAP GANGGUAN SURJA PETIR. Diploma thesis, ITPLN.

[thumbnail of (0) COVER SKRIPSI.pdf] Text
(0) COVER SKRIPSI.pdf

Download (76kB)
[thumbnail of (1) Halaman awal.pdf] Text
(1) Halaman awal.pdf

Download (182kB)
[thumbnail of BAB I.pdf] Text
BAB I.pdf

Download (90kB)
[thumbnail of BAB II.pdf] Text
BAB II.pdf

Download (549kB)
[thumbnail of BAB II.pdf] Text
BAB II.pdf

Download (549kB)
[thumbnail of BAB III.pdf] Text
BAB III.pdf
Restricted to Registered users only

Download (293kB)
[thumbnail of BAB IV.pdf] Text
BAB IV.pdf
Restricted to Registered users only

Download (253kB)
[thumbnail of BAB V.pdf] Text
BAB V.pdf
Restricted to Registered users only

Download (34kB)
[thumbnail of DAFTAR PUSTAKA DAN DAFTAR RIWAYAT HIDUP.pdf] Text
DAFTAR PUSTAKA DAN DAFTAR RIWAYAT HIDUP.pdf

Download (92kB)

Abstract

Energi dalam jumlah besar ditransmisikan melalui saluran transmisi dari pusat listrik ke Gardu Induk. Di Indonesia saluran udara dianggap lebih efektif dalam penyaluran listrik, terutama tegangan tinggi. Karena itu saluran transmisi tegangan tinggi yang melalui daerah terbuka, terutama di pegunungan memiliki tingkat kemungkinan terkena sambaran yang cukup tinggi. Petir yang menyambar saluran transmisi akan menimbulkan tegangan lebih yang akan berjalan menuju ke gardu induk dan harus di salurkan ke tanah melalui Lightning Arrester. Lightning Arrester sangat penting peranannya untuk melindungi peralatan dari tegangan lebih, peralatan yang paling mahal di Gardu Induk adalah Transformator. Transformator harus mendapat perlindungan khusus dengan memasangkan Lightning Arrester didepannya. Hasil yang diperoleh dari penelitian dengan menggunakan rumus praktis bahwa nilai tegangan impuls yang datang ke terminal transformator untuk jarak 4m yaitu sebesar 513,3 kV. Dimana besar tegangan tersebut masih jauh lebih kecil dari tingkat isolasi dasar transformator yang digunakan, yaitu 650 kV. Jarak maksimum arrester yang diperoleh yaitu 45m telah memenuhi syarat perlindungan sehingga perlindungan transformator daya terhadap gangguan surja petir sudah sangat baik.

Energy in vast amount is transmitted by transmission line from power plant to substation. In Indonesia overhead transmission is considered to be more effective in transmitting electrical energy, especially on high-voltage. Because of that high-voltage transmission going passing through an open field, more over on highlands, has a high chance of getting struck by a high voltage surge. Lightning transmission line will cause over-voltage flowing to the substation and has to be channeled to the ground through Lightning Arrester. Lightning Arrester is very essential in protecting equipment from excessive voltage, the costliest equipment on the substation is the transformer. transformer must have specialized protection by installing Lightning Arrester on its anterior. The result obtained from the research by using simple equation method is that impulse voltage coming to the transformer's terminal is 513,3 kV if the distance occur is 4m. It is far smaller than the transformer base level isolation used which is 650 kV. Maximum arrester distance amounts to 45 meters corresponding with protection standards, so the power transformer protection against lightning surge fault is exceptional.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Surja Petir, Lightning Arrester, Gardu Induk Kemayoran Lightning surge, Lightning Arrester, Kemayoran Substation.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro