PENGUJIAN DISSOLVED GAS ANALYSIS PADA MINYAK TRANSFORMATOR DI PLTA WONOGIRI

WILIYANTO, ADE and Pahiyanti, Novi Gusti (2017) PENGUJIAN DISSOLVED GAS ANALYSIS PADA MINYAK TRANSFORMATOR DI PLTA WONOGIRI. Diploma thesis, ITPLN.

[thumbnail of COVER TA.pdf] Text
COVER TA.pdf

Download (74kB)
[thumbnail of 1. Lembar pengesahan.pdf] Text
1. Lembar pengesahan.pdf

Download (66kB)
[thumbnail of 6. abstrak indonesia.pdf] Text
6. abstrak indonesia.pdf

Download (300kB)
[thumbnail of 7. abstrak bhs inggris.pdf] Text
7. abstrak bhs inggris.pdf

Download (98kB)
[thumbnail of Bab 1.pdf] Text
Bab 1.pdf

Download (154kB)
[thumbnail of BAB II TAA.pdf] Text
BAB II TAA.pdf

Download (624kB)
[thumbnail of Bab 3.pdf] Text
Bab 3.pdf
Restricted to Registered users only

Download (472kB)
[thumbnail of 15. Bab 4.pdf] Text
15. Bab 4.pdf
Restricted to Registered users only

Download (349kB)
[thumbnail of BAB V.pdf] Text
BAB V.pdf
Restricted to Registered users only

Download (38kB)

Abstract

Minyak trafo merupakan salah satu bagian dari transformator daya yang berfungsi antara lain sebagai media pendingin dan sebagai media isolasi pada trafo. Apabila terjadi gangguan pada trafo akibat dari gangguan termal maupun ganguan elektris, akan muncul gas-gas mudah terbakar dalam minyak trafo. Dengan mengetahui jenis dan jumlah gas yang ada pada minyak trafo, dapat diketahui kemungkinan gangguan yang terjadi. Metode ini dikenal dengan nama DGA (Dissolved Gas AnalyUs). Uji DGA merupakan analisis kondisi transformator yang dilakukan berdasarkan jumlah gas terlarut pada minyak transformator. Pada penelitian ini menggunakan empat metode untuk analisa kegagalan transformator yaitu metode TDCG, Key Gass, Roger’s ratio, Ratio doernenburg. Metode ini dapat menunjukan gangguan dengan lebih jelas dan detail serta merupakan metode dengan sistem tertutup sehingga mengurangi presentase kasus diluar kriteria atau kesalahan analisis. DGA merupakan pengujian minyak dengan menentukan kegagalan gas terlarut dalam minyak sehingga dapat segera di tindak lanjuti. Indikasi kegagalan yang timbul dengan thermal-selulosa pada temperatur rendah antara 150 °C - 300 °C. Dan hasil pada kadar air dan tegangan tembus pada minyak transformator dalam kondisi batasan buruk, maka perlu dilakukan purifikasi atau filter.

The transformer oil is one part of a power transformer that functions among others as a cooling medium and as an isolation medium on the traJo. If there is a disturbance in the transformer as a result of thermal disturbance or electrical disturbance, there will emerge flammable gases in transformer oil. By knowing the type and amount of gas present in transformer oil, it is possible to know the possible disturbance. This method is known as DGA (Dissolved Gas AnalyUs). DGA test is analysis transformer condition conducted based total dissolved gas in transformer oil. In this paper use four methods for analysis transformer failure that is method TDCG, Key Gass, Roger’s ratio, Ratio doernenburg. This method can show interference with clearer and details and a method with a closed system so that reduce the percentage of cases outside the criteria or error analysis. Dissolved gas analysis is an oil test by determining the failure of dissolved gas in oil so that it can be immediately followed up. Indication of failure arising with thermal-cellulose at low temperatures between 150 ° C - 300 ° C. And the results on moisture content and the breakdown voltage of the transformer oil are in poor condition, it is necessary to purify or filter.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: DGA (Dissolved Gas Analysis) Method, Oil Transformer Metode DGA (Dissolved Gas Analysis), Minyak Transformator
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Vokasi > D3 Teknologi Listrik
Depositing User: Sudarman