Pengaruh Nilai Hotspot Pada Peralatan Gardu Induk Rantau Terhadap Rugi Daya Penyaluran Sistem Tenaga Listrik

SUGIARTO, MUHAMMAD (2026) Pengaruh Nilai Hotspot Pada Peralatan Gardu Induk Rantau Terhadap Rugi Daya Penyaluran Sistem Tenaga Listrik. Diploma thesis, Institut Teknologi PLN.

[thumbnail of COVER TUGAS AKHIR.pdf] Text
COVER TUGAS AKHIR.pdf

Download (100kB)
[thumbnail of LEMBAR PENGESAHAN.pdf] Text
LEMBAR PENGESAHAN.pdf

Download (1MB)
[thumbnail of ABSTRAK.pdf] Text
ABSTRAK.pdf

Download (133kB)
[thumbnail of BAB I.pdf] Text
BAB I.pdf

Download (148kB)
[thumbnail of BAB II.pdf] Text
BAB II.pdf

Download (368kB)
[thumbnail of BAB III.pdf] Text
BAB III.pdf
Restricted to Registered users only

Download (356kB)
[thumbnail of BAB IV.pdf] Text
BAB IV.pdf
Restricted to Registered users only

Download (408kB)
[thumbnail of BAB V.pdf] Text
BAB V.pdf
Restricted to Registered users only

Download (84kB)
[thumbnail of DAFTAR PUSTAKA.pdf] Text
DAFTAR PUSTAKA.pdf

Download (120kB)
[thumbnail of Final Tugas Akhir 202371613 Muhammad Sugiarto_Muhammad Sugiarto1.pdf] Text
Final Tugas Akhir 202371613 Muhammad Sugiarto_Muhammad Sugiarto1.pdf
Restricted to Registered users only

Download (3MB)

Abstract

Hotspot pada peralatan Gardu Induk merupakan indikasi adanya peningkatan tahanan kontak yang dapat menimbulkan rugi-rugi daya dan menurunkan keandalan sistem tenaga listrik. Penelitian ini bertujuan untuk menganalisis hubungan kenaikan suhu hotspot terhadap nilai tahanan kontak serta dampaknya terhadap rugi daya penyaluran di Gardu Induk Rantau. Hasil pengukuran menunjukkan hotspot pada PMS konektor 2 fasa R sebesar 58,4 °C dengan tahanan kontak 154 µΩ, serta pada PMT konektor 2 fasa T sebesar 48,5 °C dengan tahanan kontak 218 µΩ. Kondisi tersebut menyebabkan rugi daya masing-masing sebesar 7,19 W pada PMS dan 10,17 W pada PMT. Setelah dilakukan perbaikan sambungan, rugi daya pada PMS menurun menjadi 0,62 W (efisiensi penurunan 91,37%), sedangkan pada PMT menurun menjadi 0,80 W (efisiensi 92,13%). Hasil ini menunjukkan bahwa perbaikan sambungan efektif dalam menurunkan tahanan kontak, mengurangi rugi daya, serta meningkatkan efisiensi dan keandalan sistem penyaluran tenaga listrik.

Hotspots in substation equipment indicate an increase in contact resistance that can cause power losses and reduce the reliability of the electrical power system. This study aims to analyze the relationship between hotspot temperature rise and contact resistance values, as well as their impact on power losses at Gardu Induk Rantau. The measurement results show a hotspot on the PMS connector phase R of 58.4 °C with a contact resistance of 154 µΩ, and on the PMT connector phase T of 48.5 °C with a contact resistance of 218 µΩ. These conditions resulted in power losses of 7.19 W on the PMS and 10.17 W on the PMT. After corrective maintenance was performed, the power loss on the PMS decreased to 0.62 W(a reduction efficiency of 91.37%), while on the PMT it decreased to 0.80 W (a reduction efficiency of 92.13%). These results indicate that connection repair is effective in reducing contact resistance, minimizing power losses, and improving the efficiency and reliability of the power transmission system.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Inspeksi termal, hotspot, tahanan kontak, losses, PMT, PMS
Subjects: Bidang Keilmuan > Electrical Engineering
Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Vokasi > D3 Teknologi Listrik
Depositing User: mr Muhammad Sugiarto
Date Deposited: 07 Mar 2026 15:28
Last Modified: 07 Mar 2026 15:28